2016-05-24 17:27:06 | RESIDENTIAL (R3) FRONT BUILDING, RE-ROOF BUILDING |
| REVIEW COMMENTS |
| CODE: FBC 5TH EDITION (2014). |
| |
| 1- FLAT ROOF ASSEMBLY W-51 FROM FLORIDA PRODUCT |
| APPROVAL FL2533-R15 DOESN'T MEET THE DESIGN PRESSURES |
| FOR ROOF ZONE #3. THE DESIGN PRESSURES FOR SELECTED |
| ASSEMBLY ARE -105.0 PSF. THIS PROPERTY SEEMS TO BE |
| LOCATED IN EXPOSURE "D" AND THE DESIGN PRESSURES FOR |
| ZONE #3 ARE HIGHER THAN -105.0 PSF. SEC. R301.2.1.4.3 |
| FBC-RESIDENTIAL, 5TH EDITION (2014). NEED TO PROVIDE |
| SIGNED AND SEALED RAS 117 CALCULATIONS TO MEET THE |
| DESIGN PRESSURES FOR ZONE #3, SPECIFY ANOTHER ASSEMBLY |
| THAT MEETS THE DESIGN PRESSURES FOR ZONE #3 OR PROVIDE |
| ANOTHER PRODUCT APPROVAL WITH ASSEMBLY THAT MEETS THE |
| DESIGN PRESSURES FOR ALL ROOF ZONES. NOTE: COORDINATE |
| WITH ITEM #2 BELOW REGARDING FLORIDA PRODUCT APPROVAL |
| SUBMITTED.. |
| |
| 2- PROVIDE CURRENT PRODUCT APPROVAL. FLORIDA PRODUCT |
| APPROVAL FL2533-R15 SUBMITTED WAS REVISED WITH REVISION |
| #16. PROVIDE 2 COPIES OF REVISED FL2533-R16. |
| FAC 61G20-3.002(33). |
| |
| 3- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR THE |
| GALVANIZED ROOF VENTS SPECIFIED ON THE PROPOSAL |
| SUBMITTED. FAC 61G20-3.002(33). |
| |