2016-05-20 16:47:28THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THOUGH THIS IS ONE SPRINKLER HEAD, THE ADDITION OF A
 BRAIDED FLEXIBLE ARMOVER HAS SIGNIFICANT FRITION,
 PRESSURE AND GPM LOSS THAT MAY NOT SUPPORT THE DESIGN
 OF THE SYSTEM.
  
 REVISED HYDRALIC CALCULATIONS SHALL BE SUBMITTED TO
 ESURE THE HYDRALIC DESIGN OF THE EXISTING SYSTEM IS NOT
 COMPROMISED AND WILL CONTINUE TO FUNCTION AS DESIGNED
 WITH THE BRAIDED FLEXIBLE ARMOVER.
  
 ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL
 OF THE ABOVE.
  