Plan Review Notes For Permit 16050746 |
Permit Number |
16050746 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-05-20 16:47:28 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) THOUGH THIS IS ONE SPRINKLER HEAD, THE ADDITION OF A | | BRAIDED FLEXIBLE ARMOVER HAS SIGNIFICANT FRITION, | | PRESSURE AND GPM LOSS THAT MAY NOT SUPPORT THE DESIGN | | OF THE SYSTEM. | | | | REVISED HYDRALIC CALCULATIONS SHALL BE SUBMITTED TO | | ESURE THE HYDRALIC DESIGN OF THE EXISTING SYSTEM IS NOT | | COMPROMISED AND WILL CONTINUE TO FUNCTION AS DESIGNED | | WITH THE BRAIDED FLEXIBLE ARMOVER. | | | | ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL | | OF THE ABOVE. | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|