Plan Review Notes
Plan Review Notes For Permit 16050721
Permit Number 16050721
Review Stop B
Sequence Number 2
Notes
Date Text
2016-06-13 18:08:20PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SUBSTRATE IS LISTED AS CONCRETE BLOCK ON THE
 INSTALLATION SCHEDULE FOR ALL OPENINGS AND THE SPACING
 MARKED ON THE PRODUCT APPROVAL FOR SOME OF THE STORM
 PANELS AND ACCORDIONS IS FOR POURED CONCRETE. FBC
 107.2.3 THE TABLES ARE SEPARATED INTO POURED CONCRETE
 AND CONCRETE BLOCK COLUMNS ON BOTH THE ACCORDION
 SHUTTER AND PANEL PRODUCT APPROVALS. IDENTIFY THE
 SUBSTRATE THAT YOU WILL BE FASTENING TO AND SELECT THE
 FASTENER SPACING FOR THE TYPE OF MOUNT FROM THE
 APPROPRIATE COLUMN.
  
 2) THE GLASS SEPARATION DISTANCE IS MORE THAN 1" FOR
 BOTH THE PANEL AND THE ACCORDION SHUTTER PRODUCT
 APPROVALS. PLEASE CORRECT THE INSTALLATION SCHEDULE.
 FBC R301.1
  