2016-05-16 18:26:04REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 ELECTRIC SERVICE RISER WITH WIRE SIZES, CONDUIT DETAIL
 AND GROUNDING DETAIL. COMPLETE LOAD CALCULATIONS, NEC
 215.5 RISER DIAGRAM.
  
 PROVIDE FPL AVAILABLE FAULT CURRENT LETTER , AIC
 CALCULATIONS OF OCPD AND SHORT CIRCUIT RATING OF
 ELECTRICAL EQUIPMENT. NEC 110.9, 110.10
  
 WHERE A BUILDING OR STRUCTURE HAS ANY COMBINATION OF
 FEEDERS, BRANCH CIRCUITS, OR SERVICES PASSING THROUGH
 IT OR SUPPLYING IT, A PERMANENT PLAQUE OR DIRECTORY
 SHALL BE INSTALLED AT EACH FEEDER AND BRANCH-CIRCUIT
 DISCONNECT LOCATION DENOTING ALL OTHER SERVICES,
 FEEDERS, OR BRANCH CIRCUITSSUPPLYING THAT BUILDING OR
 STRUCTURE OR PASSING THROUGH THAT
 BUILDING OR STRUCTURE AND THE AREA SERVED BY EACH. NEC
 225.37 ( IDENTIFICATION LABEL )
  
 FBC 107.3.5 PROVIDE A SITE SPECIFIC PLAN DENOTING ALL
 ELECTRICAL SERVICE APPARATUS LOCATIONS.
  