Plan Review Notes
Plan Review Notes For Permit 16050593
Permit Number 16050593
Review Stop G
Sequence Number 1
Notes
Date Text
2016-05-23 10:30:251) INDICATE THE TYPE OF PIPE AND THE SIZE OF THE PIPE
 FROM THE TANKS TO THE FIRST STAGE REGULATOR.
 2) INDICATE THE DISTANCE, THE TYPE OF PIPE AND THE SIZE
 OF THE PIPE FROM THE FIRST STAGE REGULATOR TO THE 2ND
 STAGE REGULATOR.
 3) SUBMIT TWO COPIES OF THE SIZING TABLE FOR THE PIPE
 BETWEEN THE FIRST AND SECOND STAGE REGULATOR.
 4) PER THE SIZING TABLE THAT HAS BEEN SUBMITTED, THE
 MAXIMUM BTU LOAD OF A 3/4 INCH PIPE AT 30 FT. IS
 336,000 BTU'S. SUBMIT THE CORRECT SIZING TABLE.
 5) THE LOCATION OF THE CONTAINER PRESSURE RELIEF AND
 BUILDING OPENINGS AND SOURCES OF IGNITION SHALL COMPLY
 WITH TABLE 6.3.8 OF NFPA 58.
  