Plan Review Notes
Plan Review Notes For Permit 16050593
Permit Number 16050593
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-05-17 16:43:57THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THERE IS INSUFFICIENT DETAIL PROVIDED ON THIS SUBMITTAL
 TO PROVIDE A PROPER REVIEW.
  
 1) THE INFORMATION ON THE SITE PLAN IS MINIMAL AND
 VAGUE.
  
 THE SITE PLAN SHALL INDICATE ALL ACCURATE SEPARATION
 DIMENSIONS DISTANCES FROM THE BUILDING, WINDOWS, DOORS,
 A/C INTAKES, PROPERTY LINES AND EACH TANK, IN
 COMPLAINCE WITH THE MINIMUMS DISTANCES PER NFPA.
  
 2) THERE IS NO INTERIOR FLOOR PLAN.
  
 THE BUILDING FLOOR PLAN SHALL BE INCLUDED SHOWING THE
 AREAS OF WHERE THE PIPE WILL BE INSTALLED, HOW IT WILL
 BE SECURED AND AT WHAT HEIGHT.
  
 3) IS THE BOILER A NEW INSTALLATION OR EXISTING?
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  