Notes |
Date |
Text |
2016-05-17 16:43:57 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | THERE IS INSUFFICIENT DETAIL PROVIDED ON THIS SUBMITTAL | | TO PROVIDE A PROPER REVIEW. | | | | 1) THE INFORMATION ON THE SITE PLAN IS MINIMAL AND | | VAGUE. | | | | THE SITE PLAN SHALL INDICATE ALL ACCURATE SEPARATION | | DIMENSIONS DISTANCES FROM THE BUILDING, WINDOWS, DOORS, | | A/C INTAKES, PROPERTY LINES AND EACH TANK, IN | | COMPLAINCE WITH THE MINIMUMS DISTANCES PER NFPA. | | | | 2) THERE IS NO INTERIOR FLOOR PLAN. | | | | THE BUILDING FLOOR PLAN SHALL BE INCLUDED SHOWING THE | | AREAS OF WHERE THE PIPE WILL BE INSTALLED, HOW IT WILL | | BE SECURED AND AT WHAT HEIGHT. | | | | 3) IS THE BOILER A NEW INSTALLATION OR EXISTING? | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | | | |
|