2016-05-14 14:25:04****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 5TH ED. RESIDENTIAL905.2.2, SPECIFY NUMBER OF
 LAYERS OF UNDERLAYMENT FOR THE SHINGLE PORTION OF THE
 ROOF.
  
 2. TWO COMPLETE SETS OF DOCUMENTS REQUIRED, FBC 107.
 (ONLY ONE ROOF PLAN SUBMITTED)
  
 3. THE FLAT DECK ASSEMBLY HAS A LIMITATION OF -75PSF
 WHICH DOES NOT MEET THE REQUIREMENT FOR ZONE 3 (-95.7).
 FBC 5TH ED. RESIDENTIAL 301.
  
  