Notes |
Date |
Text |
2016-05-14 14:25:04 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. FBC 5TH ED. RESIDENTIAL905.2.2, SPECIFY NUMBER OF | | LAYERS OF UNDERLAYMENT FOR THE SHINGLE PORTION OF THE | | ROOF. | | | | 2. TWO COMPLETE SETS OF DOCUMENTS REQUIRED, FBC 107. | | (ONLY ONE ROOF PLAN SUBMITTED) | | | | 3. THE FLAT DECK ASSEMBLY HAS A LIMITATION OF -75PSF | | WHICH DOES NOT MEET THE REQUIREMENT FOR ZONE 3 (-95.7). | | FBC 5TH ED. RESIDENTIAL 301. | | | | |
|