2016-05-27 11:50:51 | 5444 NORTH HAVERHILL ROAD (STADIUM & NATIONALS) - |
| PERMIT #16050576 |
| 5454 NORTH HAVERHILL ROAD (ASTROS) - PERMIT #16050577 |
| 5450 NORTH HAVERHILL ROAD (TEAM STORE) - PERMIT |
| #16050578 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| GENERAL: THE PLANS INDICATE A LOCATION OF "PALM BEACH" |
| WHICH IS A TOWN EAST OF THE CITY OF WEST PALM BEACH. |
| THE PLANS ALSO INCORRECTLY INDICATE A PLAN ADDRESS OF |
| "5300 HAVERHILL ROAD" ON SOME SHEETS AND NONE OF THE |
| SHEETS INDICATE THE ADDRESS OF 5454 NORTH HAVERHILL |
| ROAD. PLEASE CORRECTLY ADDRESS EACH OF THE PLANS. |
| |
| GENERAL: FOR EACH AREA EXPOSED TO STRUCTURE (NO |
| CEILING) INDICATE IF THE SPACE IS OBSTRUCTED |
| CONSTRUCTION OR UNOBSTRUCTED CONSTRUCTION AND INDICATE |
| THE MAXIMUM SPRINKLER DISTANCE LOCATED BELOW THE |
| STRUCTURE OR ROOF DECK (IF OBSTRUCTED CONSTRUCTION). |
| |
| SHEET FP-2 -- FIELD EQUIPMENT STORAGE #11001 (REMOTE |
| AREA #1): THE HYDRAULIC AREA SHALL BE MEASURED PARALLEL |
| TO THE BRANCH LINES PER NFPA 13. THE ROOM DESIGN METHOD |
| CANNOT BE USED AS THERE IS NO FIRE RATED WALLS |
| SEPARATING THE ROOMS. SPRINKLERS ARE LOCATED AT AN |
| ELEVATION OF ROUGHLY 12 FEET ABOVE FINISHED FLOOR; |
| HOWEVER, THE AREA IS CALCULATED AS ORDINARY HAZARD |
| GROUP 1 LIMITING THE STORAGE OF COMBUSTIBLES TO 8 FEET. |
| THIS AREA MAY NEED TO BE CALCULATED AS ORDINARY HAZARD |
| GROUP 2 TO PERMIT STORAGE GREATER THAN 8 FEET IN HEIGHT |
| OR MEASURES SHALL BE SPECIFIED AS TO HOW THE |
| COMBUSTIBLES WILL BE LIMITED TO 8 FEET. |
| |
| SHEET FP-2 -- MAINTENANCE SHOP #11125 (REMOTE AREA #2): |
| THE HYDRAULIC AREA SHALL BE MEASURED PARALLEL TO THE |
| BRANCH LINES PER NFPA 13. THE ROOM DESIGN METHOD CANNOT |
| BE USED AS THERE IS NO FIRE RATED WALLS SEPARATING THE |
| ROOMS AND THE AREA-REDUCTION METHOD FOR QUICK RESPONSE |
| SPRINKLERS CANNOT BE USED DUE TO THE EXTRA HAZARD |
| CLASSIFICATION. THE SPRINKLERS PROTECTING THE EXTRA |
| HAZARD AREA (DENSITY 0.6 GPM/SF) ARE EXTENDED COVERAGE |
| (K=11.2); HOWEVER, ACTUAL DENSITIES PROVIDED IN THE |
| HYDRAULIC CALCULATIONS (0.27 GPM/SF OR 52.5 GPM) ARE |
| WAY BELOW THE DESIGN DENSITY. FOR EXAMPLE SPRINKLER |
| #101 IS PROTECTING AN SXL AREA OF ROUGHLY 12.5' X 7.0'. |
| BEING EXTENDED COVERAGE, THE SPRINKLER AREA SHALL BE |
| ROUNDED UP AND CALCULATED USING THE "RULE OF SQUARES" |
| PER NFPA 13 SECTION 8.8.2.1.2. THIS WILL RESULT IN A |
| COVERAGE AREA OF 14'X14' OR 196 SQUARE FEET AND A |
| NEEDED FLOW OF 118 GPM PER SPRINKLER TO OBTAIN A DESIGN |
| DENSITY OF 0.6 GPM/SF. ALSO THE TYCO MODEL ELOC K=11.2 |
| THAT WAS SUBMITTED IS ONLY LISTED FOR PROTECTING LIGHT |
| HAZARD OCCUPANCIES, THIS WILL ALSO AFFECT REMOTE AREAS |
| 3 AND 4. |
| |
| SHEET FP-2: THE SPRINKLER SCHEDULE INDICATES THE |
| SPRINKLER MODEL FOR THE K=11.2 TO BE "FRB;" HOWEVER, |
| THE ACTUAL MODEL SUBMITTED IS THE "ELOC." |
| |
| SHEET FP-4: PLAN SCALE IS INDICATED AS 1/8"=1'-0" |
| HOWEVER, THE PLAN IS NOT SCALABLE. |
| |
| SHEET FP-5: THE NATIONALS LOCKER ROOM SHOWS 5 AND 6 |
| SPRINKLERS SUPPLIED BY 1-INCH BRANCH LINES. THIS |
| CONFIGURATION IS NOT SUPPORTED BY HYDRAULIC |
| CALCULATIONS. |
| |
| SHEET FP-5: WEIGHT ROOM #11318; NO SPRINKLER COVERAGE |
| FOR THE EAST PORTION OF THE ROOM. |
| |
| SHEET FP-5: STORAGE ROOM #11325, STORAGE #11220 AND |
| LAUNDRY ROOM #11313 THE SXL COVERAGE FOR ONE OR MORE |
| SPRINKLERS EXCEEDS 130 SQ.FT. |
| |
| SHEET FP-6: APPEARS THERE IS NO SPRINKLER COVERAGE IN |
| JANITOR #11430 OR NOOK DIRECTLY WEST OF THE JANITOR'S |
| ROOM. |
| |
| SHEET FP-8: STORAGE ROOM #11714 AND LAUNDRY #11706 THE |
| SXL COVERAGE FOR ONE OR MORE SPRINKLERS EXCEEDS 130 |
| SQ.FT. |
| |
| SHEET FP-12: LOBBY #11408 IS OPEN TO THE LEVEL BELOW SO |
| THE SPRINKLERS SHALL BE SUPPLIED FROM THE FLOOR BELOW |
| TO AVOID LOCATION CONFUSION WHEN THE FIRE IS ON THE |
| CLUBHOUSE LEVEL BUT THE FLOW SWITCH ALARM SHOWS THE |
| FIRE IS ON THE UPPER CONCOURSE LEVEL. COORDINATION IS |
| NEEDED WITH THE ARCHITECT -- SHEET A2.324 1ST FLOOR |
| LOBBY #11408 IS OPEN TO THE SECOND FLOOR CORRIDOR |
| #12412B. PER SECTION 8.6.9.2 UNENCLOSED VERTICAL |
| OPENINGS CREATED BY CONVENIENCE STAIRWAYS SHALL BE |
| PERMITTED AS FOLLOWS: 1) THE CONVENIENCE STAIR OPENING |
| SHALL BE PROTECTED IN ACCORDANCE WITH THE METHOD |
| DETAILED FOR THE PROTECTION OF VERTICAL OPENINGS IN |
| NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER |
| SYSTEMS UTILIZING 18" DEEP DRAFT CURTAINS AND CLOSELY |
| SPACED SPRINKLERS. |
| |
| SHEET FP-15: LOBBY #11711 IS OPEN TO THE LEVEL BELOW SO |
| THE SPRINKLERS SHALL BE SUPPLIED FROM THE FLOOR BELOW |
| TO AVOID LOCATION CONFUSION WHEN THE FIRE IS ON THE |
| CLUBHOUSE LEVEL BUT THE FLOW SWITCH ALARM SHOWS THE |
| FIRE IS ON THE UPPER CONCOURSE LEVEL. COORDINATION IS |
| NEEDED WITH THE ARCHITECT -- SHEET A2.227: 1ST FLOOR |
| LOBBY #11711 IS OPEN TO THE SECOND FLOOR RECEPTION |
| #12704. PER SECTION 8.6.9.2 UNENCLOSED VERTICAL |
| OPENINGS CREATED BY CONVENIENCE STAIRWAYS SHALL BE |
| PERMITTED AS FOLLOWS: 1) THE CONVENIENCE STAIR OPENING |
| SHALL BE PROTECTED IN ACCORDANCE WITH THE METHOD |
| DETAILED FOR THE PROTECTION OF VERTICAL OPENINGS IN |
| NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER |
| SYSTEMS UTILIZING 18" DEEP DRAFT CURTAINS AND CLOSELY |
| SPACED SPRINKLERS. |
| |
| REMOTE AREA AND HYDRAULIC CALCULATIONS (SPECIFICALLY |
| REMOTE AREAS #1, 2, 7,8, 10,12 & 14): NO AREAS INDICATE |
| THE USE OF THE ROOM DESIGN METHOD AND ONLY REMOTE AREA |
| #9 INDICATES THE USE OF THE AREA REDUCTION METHOD FOR |
| QUICK RESPONSE SPRINKLERS; HOWEVER SEVERAL OTHER AREAS |
| DO NOT CALCULATE A FULL 1,500 SQ.FT. |
| |