2016-05-18 17:03:45 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | | | - SHOW EXISTING CONDUIT, FEEDER SIZES, NEW SERVICE | | RACEWAY AND CONDUCTORS FOR 32 KW GENERATOR COMING FROM | | ATS EQUIPMENT. FBC 107 | | | | - GROUNDING DETAIL TO INCLUDE GROUNDING ELECTRODE | | CONDUCTOR SIZES IN ACCORDANCE WITH TABLE NEC 250.66 | | | | - ONE RISER INDICATES A 32 KW GENERATOR AND THE OTHER A | | 20 KW ? PLEASE CLARIFY ? DIAGRAMS DON'T MATCH. |
|