2016-05-19 09:25:14GOOD MORNING KAREN,
  
 ACCORDING TO YOUR E-MAIL IT APPEARS THAT I WAS HOLDING
 THIS JOB. THE REVISION WAS REVIEWED IN A TIMELY MANNER.
 IT WAS SUBMITTED ON MAY 12TH AND REVIEWED ON MAY 13TH.
 I RESPECTFULLY SUGGEST YOU TO REVIEW THE INFORMATION
 THAT IS SUBMITTED FOR REVIEW PRIOR TO SUBMITTAL TO
 AVOID ANY UNNECESSARY DELAYS. THE PLAN THAT WAS SIGNED
 AND SEALED BY THE ENGINEER (WILLIAM F. STUHRKE) 0N
 04/29/16 AND SUBMITTED FOR REVIEW SHOWS A 12X6 R.T.G.
 OVER DOOR. THIS GRILL SIZE IS NON-COMPLIANT. PLEASE
 COORDINATE WITH THE ENGINEER AND CONTRACTOR AND
 RESUBMIT CORRECT INFORMATION.
  
 REGARDS,
  
 JULIO C. GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
  
  
 FROM: KAREN OLIVER
 TO: "JULIO GOMEZ ([email protected])" ,
 "[email protected]" , "[email protected]"
 , "[email protected]"
 
 CC: "[email protected]" ,
 "[email protected]" , DENELLE
 
 DATE: 05/17/2016 02:44 AM
 SUBJECT: 340 WALTON BLVD. REVISION #16050496
  
 JULIO,
  
 ?PLEASE REVISIT THE ATTACHED PLAN THAT WAS REVIEWED ON
 MAY 13, 2016. YOUR RESPONSE WAS AS FOLLOWS:
  
 ?RESIDENTIAL (R3) SECOND MECHANICAL REVISION CHECKLIST.
 CODE: FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 1- TRANSFER GRILL SIZE SHOWN ON PLAN FOR MASTER BEDROOM
 AND BEDROOM #2 DOESN'T COMPLY WITH EXCEPTION #2 OF SEC.
 M1602.4 OF FBC-RESIDENTIAL, 5TH EDITION (2014). (REPEAT
 COMMENT)
 NOTE: ENGINEER OF RECORD MAY BE CHARGED FOUR TIMES THE
 PLAN REVIEW FEE EACH TIME AFTER THE THIRD REVIEW IS
 REJECTED AS REQUIRED BY FLORIDA STATUTE 553.80(2)(B).
  
 ?THIS IN FACT WAS THE REVIEW COMMENT FOR THE PREVIOUSLY
 SUBMITTED PLAN (R2), HOWEVER THE PLAN
 SUBMITTED/REVIEWED ON MAY 13 WAS THE SAME AS THE ONE
 ATTACHED AND CLEARLY HAS THE CORRECTLY SIZED BALANCED
 RETURN TRANSFER GRILLES. THERE WAS QUESTION AS TO
 WHETHER OR NOT THE BALANCE RETURNS WERE SIZED ACCORDING
 TO CODE, HENCE THE FOLLOWING IS FOR CONTRACTOR CLARITY
 PURPOSES ONLY.
  
 601.5 BALANCED RETURN AIR.
 RESTRICTED RETURN AIR OCCURS IN BUILDINGS WHEN RETURNS
 ARE LOCATED IN CENTRAL ZONES AND CLOSED INTERIOR DOORS
 IMPEDE AIR FLOW TO THE RETURN GRILL OR WHEN CEILING
 SPACES ARE USED AS RETURN PLENUMS AND FIRE WALLS
 RESTRICT AIR MOVEMENT FROM ONE PORTION OF THE RETURN
 PLENUM TO ANOTHER. PROVISIONS SHALL BE MADE IN BOTH
 RESIDENTIAL AND COMMERCIAL BUILDINGS TO AVOID
 UNBALANCED AIR FLOWS AND PRESSURE DIFFERENTIALS CAUSED
 BY RESTRICTED RETURN AIR. PRESSURE DIFFERENTIALS ACROSS
 CLOSED DOORS WHERE RETURNS ARE CENTRALLY LOCATED SHALL
 BE LIMITED TO 0.01 INCH WC (2.5 PASCALS) OR LESS.
 PRESSURE DIFFERENTIALS ACROSS FIRE WALLS IN CEILING
 SPACE PLENUMS SHALL BE LIMITED TO 0.01 INCH WC (2.5
 PASCALS) BY PROVIDING AIR DUCT PATHWAYS OR AIR TRANSFER
 PATHWAYS FROM THE HIGH PRESSURE ZONE TO THE LOW ZONE.
  
 EXCEPTIONS:
  
 1. TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER 1? TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM OR
 SPACE IT'S SERVING AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCH (25 MM) UNDERCUT TO ACHIEVE PROPER
 RETURN AIR BALANCE.
  
 2. TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (32 258
 MM2) (OF GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR
 SIZING THROUGH-THE-WALL TRANSFER GRILLES AND USING AN
 UNRESTRICTED 1 INCH (25 MM) UNDERCUTTING OF DOORS TO
 ACHIEVE PROPER RETURN AIR BALANCE.
  
 3. HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET THESE
 REQUIREMENTS FOR PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY ROOMS,
 EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE SHALL
 BE INCLUDED.
  
 ?JULIO,
  
 PLEASE APPROVE THIS AS-BUILT AT YOUR EARLIEST POSSIBLE
 CONVENIENCE, AS THIS JOB HAS BEEN LONG HELD UP WITH
 NECESSARY PLAN REVISIONS AND AS-BUILTS DUE TO THE
 COMPLEXITY AND AGE OF THE HOUSE.
  
 ?REGARDS,
  
 ?KAREN W. OLIVER
 K.O. ENERGY DESIGN, LLC
 561-327-7272? OFFICE
 561-333-0775? FAX
  
 WWW.KOENERGYDESIGN.COM
  
 ENERGY CALCS*HEAT LOADS*MECHANICAL
 DRAWINGS*COMMERCIAL*RESIDENTIAL*ENERGY RATERS
  
 ?[ATTACHMENT "WALTON M1.00 5-13.PDF" DELETED BY JULIO