Plan Review Notes
Plan Review Notes For Permit 16050432
Permit Number 16050432
Review Stop E
Sequence Number 1
Notes
Date Text
2016-05-12 19:09:50REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 - NEC 680.21(C) GFCI PROTECTION. OUTLETS SUPPLYING POOL
 PUMP MOTORS 15 OR 20 AMPERES, 125 VOLT OR 240 VOLT,
 SINGLE PHASE, WHETHER BY RECEPTACLE OR DIRECT
 CONNECTION, SHALL BE PROVIDED WITH GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL.
  
 - NEC 680.22 GFCI PROTECTION REQUIRED FOR POOL LIGHT
 CIRCUIT , AND POOL EQUIPMENT SUCH AS HEATERS, BLOWERS
 AND ETC.
  
 - PROVIDE POOL LIGHT SPECS TO VERIFY IF ITS A LISTED
 LOW-VOLTAGE LUMINAIRE NOT REQUIRING GROUNDING,
 OTHERWISE ALL POOL LIGHT ASSEMBLY . WET-NICHE AND
 DRY-NICHE SHALL BE CONNECTED TO AN INSULATED COPPER
 GROUNDING CONDUCTOR # 8 AWG. NEC 680.24