2 |
|
Notes |
Date |
Text |
2016-07-27 10:54:56 | 2ND REVIEW MECHANICAL | | PERMIT #16050413 | | 7/26/16 | | | | 1) SHEET M-1 & M-3: PROVIDE AN O/A CALCULATION FOR | | STORAGE ROOM 110 AND INDICATE HOW THE AIR WILL BE | | PROVIDED. | | | | 2) M-1: INDICATE CONTROLS OPERATION FOR EF-4. THE | | ELECTRICAL PLANS DO NOT SHOW ANY CIRCUIT OR CIRCUIT | | CONNECTION TO THE FAN. | | | | 3) M-1: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE | | WARMING OVEN. | | | | 4) M-1: INDICATE HOW CONDENSATE FROM AHU-1 IS BEING | | DRAINED AND DISCHARGED | | | | 5) PROVIDE A DETAIL FOR INSTALLATION OF THE ERV. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|