Plan Review Notes
Plan Review Notes For Permit 16050413
Permit Number 16050413
Review Stop B
Sequence Number 2
Notes
Date Text
2016-08-05 12:25:34BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16050413
 ADD: 4800 DREHER TRAIL N
 CONT: GAST CONSTRUCTION
 TEL: 561-281-1001
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. AUGUST 05/ 2016
 ACTION: DENIED
  
 1) 2ND REQUEST. PLEASE SUBMIT A SURVEY SHOWING THE
 LOCATION OF THE BUILDING THAT HOUSES THE WEST PALM
 BEACH GARDEN CLUB.
  
 1A) 2ND REQUEST. THE BUILDING APPEARS TO BE LOCATED ON
 (2) DIFFERENT LOTS. SEE PALM BEACH COUNTY PROPERTY
 APPRAISERS SITE, PCN 74-43-44-04-00-000-3010 &
 74-43-44-04-00-005-0020. BUILDINGS CAN NOT BE BUILT ON
 2 LOTS, PROPERTY LINES. 2014 FBC-B TABLE 602. A UNITY
 OF TITLE IS REQUIRED.
  
 1B) 2ND REQUEST. PLEASE ALSO ON THE SURVEY INDICATE THE
 BOUNDARIES OF THE A7 FLOOD ZONE AND THE FINISHED FLOOR
 ELEVATIONS OF THE BUILDING AND SURROUNDING MECHANICAL
 EQUIPMENT PADS. IT APPEARS THIS BUILDING LIES IN THE
 FLOOD ZONE. SECTION 94-546 (B)(2) NONRESIDENTIAL
 CONSTRUCTION. PLEASE NOTE THAT A FLOOD ELEVATION
 CERTIFICATE WAS SUBMITTED AND IF THIS RENOVATION IS
 CONSIDERED SUBSTANTIAL IMPROVEMENT THEN THE LOWEST
 ELEVATION OF EQUIPMENT SERVING THE STRUCTURE FOUND TO
 BE 11.5 FT. NGVD ON THE ELEVATION CERTIFICATE WILL ALSO
 NEED TO BE ELEVATED TO THE MINIMUM ELEVATION OF 12.5
 FT. NGVD.
  
 1C)2ND REQUEST. THE P. B. C. PROPERTY APPRAISERS OFFICE
 DOES NOT PROVIDE THE CURRENT VALUE OF THE STRUCTURE
 BEFORE THE ALTERATIONS THAT ARE TO TAKE PLACE. UNTIL A
 VALUE FOR THE STRUCTURE IS KNOWN, SUBSTANTIAL
 IMPROVEMENT FOR THIS BUILDING CANNOT BE DETERMINED, NOR
 IF COMPLIANCE WITH SUBSTANTIAL IMPROVEMENT IS REQUIRED.
 SEE CITY WEST PALM BEACH MUNI-CODE;
 SECTION 94-611 DEFINITIONS. SUBSTANTIAL IMPROVEMENT.
 SECTION 94-546 (B)(2) NONRESIDENTIAL CONSTRUCTION.
 2014 FBC-B 1612.4 DESIGN AND CONSTRUCTION. THE DESIGN
 AND CONSTRUCTION OF BUILDINGS AND STRUCTURES LOCATED IN
 FLOOD HAZARD AREAS, INCLUDING COASTAL HIGH HAZARD
 AREAS, SHALL BE IN ACCORDANCE WITH CHAPTER 5 OF ASCE 7
 AND WITH ASCE 24.
  
 2-4) COMPLIED.
  
 5) 2ND REQUEST. MISSING PRODUCT APPROVALS: 2010 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 6) 2ND REQUEST. 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 7) 2ND REQUEST, THE STRUCTURAL SHEETS SHOW STEEL
 FRAMING TO BE ADDED TO A BAR JOIST SYSTEM, M5 NOW SHOWS
 ANCHORING OF THE RTU?S CURB TO A CONCRETE DECK AND
 ANCHORING THE CURB TO THE DECK WITH REDHEADS. HOW IS
 THE DECK PART OF THE MWFRS? 2014 FBC-B 1604.4 ANALYSIS.
  
 1ST ROUND OF COMMENTS. SHEET M2 SHOWS ROOFTOP UNITS
 THAT WILL SIT ON ROOF TOP CURBS. NEITHER THE MECHANICAL
 NOR STRUCTURAL SHEETS SHOW HOW THESE UNITS ARE TO BE
 MOUNTED. SHEET M2 NOTE # 1 INDICATES THESE RTU'S ARE
 NEW UNITS. PLEASE PROVIDE FOR THE ADDITIONAL FRAMING
 AROUND THE NEW ROOF TOP PENETRATIONS, IF FRAMING
 MEMBERS WERE CUT, THE REINFORCEMENT AND HOW THE
 ADDITIONAL POINT LOADS WERE HANDLED? PLEASE ALSO
 PROVIDE THE CONNECTION OF THE ROOFTOP CURB TO THE ROOF
 FRAMING MEMBERS, THE ANCHORAGE OF THE RTU TO THE CURB.
  
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS
  
 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 8-9) COMPLIED
  
 10) THE PROJECT INDICATES A DOLLAR VALUE OF
 $400,000.00. PLEASE PROVIDE A LIST OF ALL ACCESSIBLE
 FEATURES THAT ARE GOING TO BE CORRECTED AND THEIR
 DOLLAR AMOUNT. UP TO $80,000.00 IN VALUE. AT THIS POINT
 THE DISPROPORTIONATE COST HAVE BEEN MET. CONTRACTOR IS
 TO SUBMIT AN ITEMIZED LIST OF ELEMENTS WHERE THESE
 FUNDS HAVE BEEN SPENT IN ACCESSIBLE UPGRADES. THE LIST
 SHOULD FOLLOW THE SAME ORDER AS IN SECTION 202.4.2 IN
 CHOOSING WHICH ACCESSIBLE ELEMENTS TO PROVIDE, PRIORITY
 SHOULD BE GIVEN TO THOSE ELEMENTS THAT WILL PROVIDE THE
 GREATEST ACCESS, IN THE FOLLOWING ORDER: (I) AN
 ACCESSIBLE ENTRANCE; (II) AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (III) AT LEAST ONE ACCESSIBLE RESTROOM
 FOR EACH SEX OR A SINGLE UNISEX RESTROOM; (IV)
 ACCESSIBLE TELEPHONES; (V) ACCESSIBLE DRINKING
 FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION15110652
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  