2016-05-19 07:18:341ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16050413
 5/19/16
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS- SECTION
 C403.2.1 FBC-14 ENERGY CALCULATION.
 2) PROVIDE ENERGY CALCULATIONS- C101.4.3 FBC-14 ENERGY
 CONSERVATION.
 3) SHEET M-3: THE OUTSIDE AIR HAS BEEN CALCULATED USING
 OFFICES AS THE BASIS OF DESIGN, HOWEVER THIS IS AN
 ASSEMBLY OCCUPANCY PER THE ARCHITECT. IT APPEARS THAT
 THE OCCUPANCY DENSITIES AND AIRFLOW RATES IN THE
 CALCULATIONS DO NOT MATCH THE INTENDED USE OF THE ROOMS
 AND SPACES.
 4) M3: THE EXHAUST RATE FOR TOILETS OR URINALS IS 70
 CFM PER FIXTURE FOR INTERMITTENT USE- TABLE 403.3
 FOOTNOTE E. EF 1 & 2 SHALL BE MINIMUM 210 CFM'S EACH.
 5) M-1: A DUCT SMOKE DETECTOR IS REQUIRED IN THE RETURN
 AIR SYSTEM OF AHU-1 PER SECTION 606.2.1
 6) M-1: REFER TO SECTION 507.2.2 AND PROVIDE A TYPE II
 HOOD FOR THE WARMING OVEN OR PROVIDE EXHAUST
 VENTILATION AT A RATE OF 0.70 CFM'S PER SF.
 7) M-5: PROVIDE SITE SPECIFIC WIND LOAD ENGINEERING FOR
 THE RTU'S PER SECTION 301.15. PROVIDE ON THE PLAN A
 SECTION CUT THAT SHOWS THE ROOF OPENING REINFORCEMENTS,
 CURB CONSTRUCTION AND ANCHORAGE, CURB HEIGHT, AND RT&U
 MOUNTING DETAILS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  