Plan Review Notes For Permit 16050413 |
Permit Number |
16050413 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-05-19 07:18:34 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #16050413 | | 5/19/16 | | | | 1) PROVIDE AC COOLING AND HEATING CALCULATIONS- SECTION | | C403.2.1 FBC-14 ENERGY CALCULATION. | | 2) PROVIDE ENERGY CALCULATIONS- C101.4.3 FBC-14 ENERGY | | CONSERVATION. | | 3) SHEET M-3: THE OUTSIDE AIR HAS BEEN CALCULATED USING | | OFFICES AS THE BASIS OF DESIGN, HOWEVER THIS IS AN | | ASSEMBLY OCCUPANCY PER THE ARCHITECT. IT APPEARS THAT | | THE OCCUPANCY DENSITIES AND AIRFLOW RATES IN THE | | CALCULATIONS DO NOT MATCH THE INTENDED USE OF THE ROOMS | | AND SPACES. | | 4) M3: THE EXHAUST RATE FOR TOILETS OR URINALS IS 70 | | CFM PER FIXTURE FOR INTERMITTENT USE- TABLE 403.3 | | FOOTNOTE E. EF 1 & 2 SHALL BE MINIMUM 210 CFM'S EACH. | | 5) M-1: A DUCT SMOKE DETECTOR IS REQUIRED IN THE RETURN | | AIR SYSTEM OF AHU-1 PER SECTION 606.2.1 | | 6) M-1: REFER TO SECTION 507.2.2 AND PROVIDE A TYPE II | | HOOD FOR THE WARMING OVEN OR PROVIDE EXHAUST | | VENTILATION AT A RATE OF 0.70 CFM'S PER SF. | | 7) M-5: PROVIDE SITE SPECIFIC WIND LOAD ENGINEERING FOR | | THE RTU'S PER SECTION 301.15. PROVIDE ON THE PLAN A | | SECTION CUT THAT SHOWS THE ROOF OPENING REINFORCEMENTS, | | CURB CONSTRUCTION AND ANCHORAGE, CURB HEIGHT, AND RT&U | | MOUNTING DETAILS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|