2016-05-19 11:28:29INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL
 LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE
 ALARM, ACCESS CONTROLS (GATES), CCTV, PHONE AND DATA,
 WIRELESS SYSTEMS, ETC. A NOTE WILL SUFFICE.
 2. ADD A GENERAL NOTE TO PROVIDE PER FBC EC 405.7.4-
 COMPLETION DOCUMENTS PER CODE SECTION.
 3. LABEL MAINS TO INDICATE MAIN 1 OF 2 AND 2 OF 2, FOR
 THE 400A SERVICE SHOWN. NEC 230.2
 4. SHOW ON PANEL BOARD SCHEDULE ALL BRANCH CIRCUIT
 CONDUCTOR SIZES. FBC 107.3.5
 5. LABEL CIRCUIT LA-15 TO BE GFCI PROTECTED FOR THE
 DRINKING FOUNTAIN. NEC 422.52
 6. PLEASE LABEL THE KITCHEN RECEPTACLE OUTLET WITHIN
 6FT OF SINK TO BE GFCI PROTECTED. NEC 210.8B2 AND NOTE
 THAT ALL 125V 20A RECEPTACLES WITHIN THE FOOD
 PREPARATION AREA TO BE LABELED GFCI ALSO. NEC 210.8B5
 7. ADDRESS ALL FIRE COMMENTS RELATED TO ELECTRICAL
 SHEETS, EXIT LIGHTING, HOOD AND FIRE ALARM DRAWINGS.
 8. PROVIDE A GENERAL NOTE TO INDICATE THE REQUIREMENTS
 OF NEC 410.130G1- DISCONNECTING MEANS FOR ALL DOUBLE
 ENDED LAMPS.
 9. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  