2016-05-13 09:26:22 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16050374 |
| ADD: 400 S. CONGRESS AVE. |
| CONT: LLOYD'S ROOFING |
| TEL: 561-312-0803 |
| E-MAIL: |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: FRI. MAY 13/16 |
| ACTION: BUILDING PROVISO |
| |
| 1) ROOFING: NOTICE: EFFECTIVE APRIL 1/2016 THE |
| REFERENCED MIAMI-DADE COUNTY ELECTROGALVANIZED |
| FASTENERS LISTINGS ARE SUSPENDED: |
| 11--1019.02 & 11-1019.03 BLUELINX CORP. |
| 12-0423.06 CONTINENAL MATERIALS, INC. |
| 15-1123.04 PRIME SOURCE BUILDING PRODUCTS, INC. |
| 13-0530.01 SPECIALTY FASTENING SYSTEM |
| 12-0423.03 & 12-0423.04 SUMMIT CONGLOMERATE, LLC |
| 12-1205.11, 12-1205.13 & 13-05 & 13-0514.05 WEATHERPRO, |
| LLC |
| |
| 2) R905.2.7 UNDERLAYMENT APPLICATION. <4/12 PITCH. |
| UNDERLAYMENT SHALL BE INSTALLED USING ONE OF THE |
| FOLLOWING METHODS: 1. FOR ROOF SLOPES FROM TWO UNITS |
| VERTICAL IN 12 UNITS HORIZONTAL (17-PERCENT SLOPE), AND |
| LESS THAN FOUR UNITS VERTICAL IN 12 UNITS HORIZONTAL |
| (33-PERCENT SLOPE). UNDERLAYMENT SHALL COMPLY WITH ASTM |
| D 226, TYPE I OR TYPE II OR ASTM D 4869, TYPE II OR |
| TYPE IV OR ASTM D 6757 AND SHALL BE TWO LAYERS APPLIED |
| IN THE FOLLOWING MANNER. APPLY A 19-INCH (483 MM) STRIP |
| OF UNDERLAYMENT FELT PARALLEL TO AND STARTING AT THE |
| EAVES, FASTENED SUFFICIENTLY TO HOLD IN PLACE. STARTING |
| AT THE EAVE, APPLY 36-INCH-WIDE (914 MM) SHEETS OF |
| UNDERLAYMENT, OVERLAPPING SUCCESSIVE SHEETS 19 INCHES |
| |