Plan Review Notes
Plan Review Notes For Permit 16050338
Permit Number 16050338
Review Stop P
Sequence Number 1
Notes
Date Text
2016-05-16 16:51:441ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHOW HEIGHT AND CLEAR FLOOR SPACE OF URINAL SHALL
 COMPLY WITH FBC PL SEC .605
 606.2 CLEAR FLOOR SPACE.
  
 2. SHOW CLEAR FLOOR SPACE FOR LAVATORY'S.THE CHASE IN
 MENS BATHROOM FOR THE ELECTRIC SHALL NOT ENCROACH ON
 CLEAR FLOOR SPACE FOR URINAL. SHALL COMPLY WITH FBC ACC
 606.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 3. SHOW MIN 33 AND MAX 36 MEASURED FROM TOP OF GRIPPING
 FOR GRAB BARS FBC ACC. 609.4 POSITION OF GRAB BARS.
  
 4. SHOW COMPLIANCE WITH FBC ACC. 604.5.1 SIDE WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL
  
 5. SHOW SAMPLING PORT FOR GREASE SYSTEM DOWN STREAM OF
 CLEAN OUT ON OUTLET SIDE OF TANK SHALL BE 6IN. SEE WPB
 UTILITIES STANDARD DETAIL GS-7