2016-05-19 11:53:371ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16050338
 5/19/16
  
  
 1) SUBMIT AC COOLING AND HEATING CALULATIONS- SECTION
 C403.2.1 FBC-14 ENERGY CONSERVATION.
 2) SUBMIT ENERGY CALCULATIONS- SECTION C101.2 FBC-14
 ENERGY.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE PIZZA
 OVEN AND EXHAUST DUCT. PLEASE NOTE A SEPARATE PERMIT IS
 REQUIRED FOR KITCHEN HOOD AND EXHAUST EQJUIPMENT. A)
 PROVIDE A FRONT VIEW OF THE HOOD AND DUCT SHOWING THE
 TOTAL RUN LENGTH OF THE DUCT, HOW THE DUCT WILL BE
 SUPPORTED, CLEARANCE DISTANCES TO COMBUSTIBLES, DUCT
 THROUGH-ROOF PENETRATION DETAILS, AND TERMINATION
 HEIGHT ABOVE THE ROOF- SEE SECTIONS 503.6.4, 503.6.5,
 AND TABLE 504.2(1) FBC-14 FUEL GAS.
 4) SEPARATE PERMIT IS REQUIRED FOR WALK-IN COOLERS-
 PLACE A NOTE ON THE PLANS.
 5) M-2: DINING ROOM VENTILATION RATE IS CALCULATED
 USING AN OCCUPANT DENSITY OF 70 PERSONS PER 1000 SF.
 PLEASE REVISE THE CALCULATION
 6) M-2: KITCHENS HAVE A REQUIRED EXHAUST RATE OF 0.70
 CFMS PER SF. AND THE AIR FROM THAT SPACE SHALL NOT BE
 RECIRCULATED- TABLE 403.3 FOOTNOTE B.
 7) INDICATE HOW ACCESS TO THE ROOF TOP MECHANICAL
 EQUIPMENT WILL BE PROVIDED- SEE SECTION 306.5
 8) SUBMIT A FLORIDA PRODUCT APPROVAL AND/OR MIAMI-DADE
 NOA FOR THE ROOF STAND WITH APPROVAL SIGNATURE BBY EOR.
 THE EOR SHALL CIRCLE, HIGHLIGHT, OR OTHERWISE MARK ALL
 APLLICABLE DETAILS, DESIGN PRESSURES, AND ANCHORING AND
 FASTENING DETAILS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  