2016-05-09 17:05:591ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 THE APPLICATION DESCRIPTION INCLUDES ELECTRICAL AND
 PLUMBING WORK. THE APPLICANT APPEARS TO BE AN
 ELECTRICIAN. PLEASE CLARIFY IF YOU INTEND TO INSTALL A
 WATER HEARTR AND PERFORM THE ASSOCIATED PLUMBING WORK.
 IF SO, PLEASE INDICATE THE REQUIRED QUALIFICATION FOR
 THIS WORK PURSUANT TO FS 489, OR THE PBC CILB RULES.
  
 THE APPLICATION DESCRIPTION INDICATES A NEW ELECTRICAL
 SERVICE IS TO BE PROVIDED. PLEASE PROVIDE A RISER
 DIAGRAM PER THE MINIMUM PLAN REVIEW CRITERIA OF FBC 107
 TO INCLUDE ELECTRIC SERVICE RISER WITH WIRE SIZES,
 CONDUIT DETAIL AND GROUNDING DETAIL. ADDITIONALLY, IT
 MAY BE NECESSARY TO PROVIDE COMPLETE LOAD CALCULATIONS
 AND A PANEL SCHEDULE OR TO OTHERWISE NOTE THE EXISTING
 CONDITION.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  