Plan Review Notes
Plan Review Notes For Permit 16050249
Permit Number 16050249
Review Stop M
Sequence Number 3
Notes
Date Text
2016-08-15 11:57:033RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16050249
 8/15/16
  
 1) THE ENERGY/GAUGE SUBMITTAL INDICATES AHU-5 TO HAVE A
 CAPACITY OF 284 MBH HOWEVER THE AC SCHEDULE INDICATES
 316 MBH- PLEASE CORRECT ONE OR THE OTHER.
  
 2) THE AC SYSTEMS APPEAR TO BE OVERSIZED AND NOT IN
 COMPLIANCE WITH SECTION C403.2.2 FBC-14 ENERGY
 CONSERVATION. THE AC CALCULATIONS INDICATE A TOTAL HEAT
 LOAD OF 62.8 TON HOWEVER THE SCHEDULE INDICATES 75 TONS
 OF COOLING. THE CALCULATIONS INDICATE A HEATING COIL
 REQUIREMENT OF 76 KW, HOWEVER THE SCHEDULE INDICATES 95
 KW ELECTRIC HEAT SELECTED- SEE SECTION C403.2.2 FBC-14
 ENERGY CONSERVATION.
  
 3) THE ZONE LOCATIONS INDICATED IN THE AC CALCULATIONS-
 EAST, WEST, CENTRAL, LOCKERS, STR COND DO NOT MATCH THE
 AHU LOCATIONS SHOW IN THE SCHEDULE- SOUTH, STRENGTH,
 NORTH, HOSPITALITY, & SOUTH O/A. PLEASE CORRELATE THE
 CALCS WITH THE SYSTEMS AND THE PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER