Plan Review Notes
Plan Review Notes For Permit 16050249
Permit Number 16050249
Review Stop B
Sequence Number 3
Notes
Date Text
2016-08-16 08:11:36****CORRECTIONS****
 REVISED 9/7 (ITEM 34)
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 GOVERNING CODE: FBC 5TH EDITION (FBC 2014)
  
 1. FLORIDA STATUTE 553.71, IT APPEARS THAT THIS
 BUILDING MAY QUALIFY AS A THRESHOLD BUILDING; ANY
 BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DEFINED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SF IN AREA AND AN OCCUPANT CONTENT
 OF GREATER THAN 500 PERSONS.
  
 2. AS A THRESHOLD BUILDING, THE FOLLOWING IS REQUIRED:
  
 A. THRESHOLD INSPECTION PLAN; FS 553.79(5)(A), CITY OF
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 109.3.6.1. THE
 ENFORCING AGENCY SHALL REQUIRE A SPECIAL INSPECTOR TO
 PERFORM STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING
 PURSUANT TO A STRUCTURAL INSPECTION PLAN PREPARED BY
 THE ENGINEER OR ARCHITECT OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO AND APPROVED BY
 THE ENFORCING AGENCY BEFORE THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 B. THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FS
 553.79(5)(A) TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES, NOTARIZED AND RETURNED
 TO THIS OFFICE, REVIEWED AND APPROVED PRIOR TO PERMIT
 ISSUANCE. CONTACT KEN CONRAD, MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM, AT 561-805-6666 FOR ADDITIONAL
 INFORMATION.
 FORMS WERE SENT TO: [email protected]
 ON 5/28/16.
  
 C. SPECIAL INSPECTOR RESUME': PROVIDE A RESUME' OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECTS FOR REVIEW
 BY THE BUILDING OFFICIAL OR HIS DESIGNEE. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
 UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED
 FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA. THE
 RESUME' IS TO BE SUBMITTED TO KEN CONRAD (AND COPY
 SAMANTHA HILL), 561-805-6666, [email protected],
 [email protected]
  
 ALL PROSPECTIVE INSPECTORS ARE TO BE APPROVED BY THE
 CHIEF BUILDING INSPECTOR AND ALL ARE REQUIRED TO SIGN
 THE SPECIAL INSPECTOR AGREEMENT.
  
 D. CONTRACTOR RESUME': PROVIDE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE SUBMITTED TO
 KEN CONRAD, (PLEASE COPY SAMANTHA HILL) VIA E-MAIL
 ([email protected], [email protected]).
  
 E. PERMIT DOCUMENTS: PAPER SUBMITTALS REQUIRE THREE
 SIGNED AND SEALED (IF APPLICABLE) ORIGINAL SETS OF ALL
 DOCUMENTS.
  
 F. THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 MINIMUM BUILDING CODES AND THE APPLICABLE FIRESAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS CHAPTER AND CHAPTER 633.
  
 (ARCHITECT OK - REVISED PLAN)
  
 THE ENGINEER HAS A SIMILAR STATEMENT BUT LACKS SOME OF
 THE STATUTORY LANGUAGE; PLEASE REVISE.
  
 3. ADVISORY ONLY; PER FS 553.79, ALL SHORING/RE-SHORE
 ENGINEERING IS TO BE REVIEWED BY ENGINEER OF RECORD
 AND THREE SIGNED AND SEALED ORIGINAL SETS ARE TO BE
 SUBMITTED FOR PLAN REVIEW. THE SHORING/RESHORE
 ENGINEERING IS TO BE REVIEWED AND APPROVED PRIOR TO
 INSPECTION. THE CITY APPROVED (CITY STAMPED)
 SHORING/RE-SHORE ENGINEERING IS TO BE AVAILABLE ON THE
 JOB AT THE TIME OF INSPECTION.
  
 4. ADVISORY ONLY; PRIOR TO INSTALLATION, A GUARD RAIL
 DETAIL IS TO BE SUBMITTED FOR PLAN REVIEW. THIS SHOULD
 BE SUBMITTED WITH THE SHORING/RESHORE ENGINEERING.
  
 5. SEE IMPACT FEE REVIEW.
  
 6. ADVISORY ONLY; SEE ROOF (R STOP) REVIEW. NO ROOFING
 INFORMATION PROVIDED IF ROOFING INFORMATION (PRODUCT
 APPROVAL REVIEWED BY DESIGNER OF RECORD, ASSEMBLY
 PROPOSED, ENHANCED FASTENING CALCULATIONS IF REQUIRED)
 IS NOT SUBMITTED PRIOR TO PERMIT ISSUANCE, THIS PERMIT
 WILL BE ISSUED WITH PROVISO. ROOF INFORMATION WILL BE
 REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED PRIOR
 TO INSTALLATION.
  
 9. THREE COMPLETE SETS OF PLANS REQUIRED FOR ALL
 THRESHOLD JOBS (CITY, CONTRACTOR, THRESHOLD INSPECTOR).
  
 11 TO 18. OK
  
 19. LS101, ACADEMICS TEAM ROOM OCCUPANT LOAD IS SHOWN
 AS 20 SF PER PERSON, CLARIFY, APPEARS TO BE A TYPO AS
 THIS SHOULD BE 15 SF (AND OCC LOAD CALCULATED USING 15
 SF). REVISE PLAN TO CLARIFY USE OF THE SPACE. 15SF IS
 FOR AREAS WITH TABLES AND CHAIRS, AREAS WITH CHAIRS
 ONLY SHOULD USE 7 SF, AND STANDING AREAS SHOULD USE
 5SF.
  
 2ND REVIEW, ARCHITECT?S RESPONSE IS ACCEPTABLE. PLEASE
 REVISE PLAN TO NOTE THAT ACADEMICS TEAM ROOM IS A
 CLASSROOM, ACCESSORY USE.
  
 20. LS101, THE ACADEMICS TEAM ROOM MEANS OF EGRESS
 FORCES THE OCCUPANT TO TRAVEL THROUGH A SPACE WHICH IS
 A WORK AREA, WHICH APPEARS TO BE PROHIBITED BY FBC
 1014.2. REVISE PLAN TO EITHER MODIFY EXITING STRATEGY
 OR REVISE PLAN TO SHOW COMPLIANCE (I.E., SHOW HOW THE
 TWO SPACES ARE ACCESSORY TO ONE ANOTHER).
  
 2ND REVIEW, RESPONSE STATES THAT DIRECT ACCESS TO THE
 CORRIDOR WAS PROVIDED. PLEASE SEE LS101; THE NEW ACCESS
 TO CORRIDOR APPEARS TO BE LABELED STORAGE ON ALL
 SHEETS. PLEASE REVISE THE LIFE SAFETY AND FLOOR PLAN.
 IT APPEARS THAT THE STORAGE ROOM MAY BE THE ADJACENT
 ROOM. ALSO PLEASE INCLUDE THE DIMENSION BETWEEN THE TWO
 DOORS TO SHOW COMPLIANCE WITH FBC 5TH EDITION
 ACCESSIBILITY FIGURE 404.2.6.
  
 24 - 27. OK
  
 30. OK
  
 31 TO 33. OK
  
 34. REVISED 9/7 - RECEIVED LETTER FROM ENGINEER
 REGARDING RATIONALE FOR RISK CATEGORY II. LETTER IS
 ACCEPTABLE; PLEASE INCLUDE THE SIGNED, SEALED ORGINAL
 WITH THE RESUBMITTAL.
  
 35. OK
  
 36. FBC 1008.1.10, REVISE DOOR SCHEDULE AE701 TO
 INCLUDE DOOR HARDWARE; IT IS NOT CLEAR WHERE PANIC
 HARDWARE IS PROPOSED.
  
 FBC TABLE 716.5, EXIT ENCLOSURES REQUIRE 1 HOUR DOORS;
 DOOR 101 PROPOSES 20 MIN, PLEASE REVISE.
  
 ALSO, REGARDING THIS EXIT STAIR WHICH DISCHARGES INTO
 THE FIRST FLOOR, SEE FBC 1027.1 EXCEPTION 1.1, THE EXIT
 IS TO BE READILY VISIBLE AND IDENTIFIABLE FROM THE
 POINT OF TERMINATION OF THE ENCLOSURE. PLEASE SEE
 CLARIFICATION IN THE COMMENTARY, WHICH SPECIFICALLY
 STATES THAT THE OCCUPANT SHOULD NOT BE REQUIRED TO TURN
 COMPLETELY AROUND OR AROUND A CORNER. IT APPEARS THAT
 EITHER THE DOOR SHOULD OPEN DIRECTLY INTO THE DIRECTION
 OF THE EXIT DISCHARGE OR THE WALL AT THE END OF THE
 FIRST FLOOR STAIR SHOULD BE RATED THE SAME AS THE STAIR
 IF THIS IS TO BE CONSIDERED A CONTINUATION OF THE STAIR
 EXIT.
  
 37. FROM PREVIOUS LIST: A SPOT CHECK OF THE ENERGY
 CALCS WAS DONE; PLEASE CLARIFY THE FOLLOWING OR REVISE
 PLAN:
 ROOF INSULATION IS R20 ON ENERGY CALCS, R19 ON PLAN
  
 2ND REVIEW, THIS WAS CORRECTED BUT STILL SPECS R19 IN
 SOME LOCATIONS (SEE AE320, AE321). PLEASE REVISE AND
 CHECK ALL.
  
 38. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING
 PROVISOS:
  
 COMPONENTS AND CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED, REVIEWED AND
 APPROVED PRIOR TO INSTALLATION
  
 SEPARATE PERMITS, PLANS, REVIEWS, AND FEES WILL BE
 REQUIRED FOR SIGNS, AWNINGS, PARKING
  
 NEW COMMENT:
  
 39. PLAN REVIEW NOTE: THIS PLAN WAS RESUBMITTED PRIOR
 TO BUILDING PLAN REVIEW #2.
  
 PLEASE SEE FS553.80 (NOTE LANGUAGE "SHALL IMPOSE"
 RATHER THAN "MAY"):
 (B)"WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS'
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 FOR THIS PROJECT, PLAN REVIEW FEE IS $22,637 (4X FEE =
 $90,548). IF DESIGN PROFESSIONAL DISAGREES WITH A
 SIGNIFICANT PLAN REVIEW COMMENT FOR ANY PROJECT, IT IS
 RESPECTFULLY SUGGESTED THAT THE APPROPRIATE REVIEWER BE
 CONTACTED AND RESOLVE PRIOR TO RESUBMITTING. ALTHOUGH
 LANGUAGE REQUIRES THAT THE FEE BE IMPOSED, IT IS NOT
 BEING IMPOSED AT THIS TIME DUE TO THE FACT THAT SINCE
 PLANS WERE RESUBMITTED WITHOUT ADDRESSING BUILDING
 COMMENTS FROM REVIEW 1, THIS IS BUILDING REVIEW 2
 RATHER THAN BUILDING REVIEW 3. PLEASE ALLOW ALL TRADES
 TO COMPLETE REVIEWS PRIOR TO RESUBMITTAL.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved