2016-07-27 11:30:11 | 2ND REVIEW |
| |
| |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER LL |
| CITY OF WEST PALM BEACH |
| DEVELOPMENT SERVICES |
| BUILDING DIVISION |
| 561-805-6711 |
| [email protected] |
| |
| |
| PLUMBING COMMENTS: |
| |
| 1. SHOW DIMENSION OF WATER CLOSET OF SIDE WALL. PER FBC |
| ACC 604.2 LOCATION. |
| THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR |
| PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE |
| OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM |
| TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR |
| PARTITION, EXCEPT THAT THE WATER CLOSET SHALL BE 17 |
| INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM |
| FROM THE SIDE WALL OR PARTITION IN THE AMBULATORY |
| ACCESSIBLE TOILET COMPARTMENT SPECIFIED IN 604.8.2. |
| WATER CLOSETS SHALL BE ARRANGED FOR A LEFT-HAND OR |
| RIGHT-HAND APPROACH. |
| |
| 2. SHOW CLEARANCE AROUND WATER CLOSET TO COMPLY WITH |
| FBC ACC 604.3.1 SIZE. |
| CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES |
| (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE |
| WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED |
| PERPENDICULAR FROM THE REAR WALL. |
| |
| |
| 3. PREVIOUS COMMENT 16) SHT. P0.03 - SUBMIT |
| MANUFACTURER'S SPECIFICATIONS FOR THE OIL GUARD SUMP |
| PUMP SYSTEM. FPC SEC.1003.4 - EXCEPTION. THE DETAIL YOU |
| PROVIDED ON P0.03 IS NOT WHAT WE ARE LOOKING FOR. WE |
| WANT THE SPECIFICATION SHEETS FROM THE SPECIFIC |
| MANUFACTURE FOR THE PUMP AND OIL GUARD SYSTEM. PER WPB |
| AMEND. TO FBC 107.2.1 |
| |
| 4. PREVIOUS COMMENT 17) SHT.P0.03 - CONDENSATE BOX |
| DETAIL - HOW WILL THE POSSIBILITY OF WATER SPILLAGE BE |
| CONTROLLED WITH THIS DEVICE? CLARIFY. THIS DETAIL DOES |
| NOT SHOW US HOW SPILLAGE WILL BE CONTROLLED. PLEASE |
| CLARIFY PER WPB AMEND. TO FBC 107.2.1 |
| |
| 5. PREVIOUS COMMENT 18) SUBMIT A CONDENSATE RISER FOR |
| REVIEW. SHOW THE TERMINATION POINT OF THE CONDENSATE |
| DRAINS. FBC 107.1. YOU RESPONDED THAT A RISER WAS ADDED |
| BUT COULD NOT FIND IT PLEASE CLARIFY. |
| |
| 6. SHT. P0.03 DETAIL FOR WATER HEATER. THE RETURN LINE |
| OF THE RECIRCULATION SYSTEM SHALL SHOW THAT IT CONNECTS |
| TO BOTH THE COLD INLET OF THE WATER HEATER AND THE COLD |
| WATER INLET OF THE THERMOSTATIC MIXING VALVE . PER FBC |
| PL SEC. 607.2.2 |
| |
| 7. SHT. P1.04+P3.03 SNK 1+2 SHALL BE PROVIDE WITH HOT |
| OR TEMPERED WATER. PER FBC PL 607.1 |
| |
| 8. SHT. P3.02 SHOW WATER HAMMER ARRESTOR ON ICE |
| MACHINE. PER FBC PL 604.9 |
| |
| 9. PLEASE SHOW FLOW ARROWS ON HOT WATER RETURN SYSTEM . |
| PER WPB AMEND TO FBC 107.2.1 |
| |
| |