2016-07-27 11:30:112ND REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1. SHOW DIMENSION OF WATER CLOSET OF SIDE WALL. PER FBC
 ACC 604.2 LOCATION.
 THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM
 TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION, EXCEPT THAT THE WATER CLOSET SHALL BE 17
 INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM
 FROM THE SIDE WALL OR PARTITION IN THE AMBULATORY
 ACCESSIBLE TOILET COMPARTMENT SPECIFIED IN 604.8.2.
 WATER CLOSETS SHALL BE ARRANGED FOR A LEFT-HAND OR
 RIGHT-HAND APPROACH.
  
 2. SHOW CLEARANCE AROUND WATER CLOSET TO COMPLY WITH
 FBC ACC 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
  
  
 3. PREVIOUS COMMENT 16) SHT. P0.03 - SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE OIL GUARD SUMP
 PUMP SYSTEM. FPC SEC.1003.4 - EXCEPTION. THE DETAIL YOU
 PROVIDED ON P0.03 IS NOT WHAT WE ARE LOOKING FOR. WE
 WANT THE SPECIFICATION SHEETS FROM THE SPECIFIC
 MANUFACTURE FOR THE PUMP AND OIL GUARD SYSTEM. PER WPB
 AMEND. TO FBC 107.2.1
  
 4. PREVIOUS COMMENT 17) SHT.P0.03 - CONDENSATE BOX
 DETAIL - HOW WILL THE POSSIBILITY OF WATER SPILLAGE BE
 CONTROLLED WITH THIS DEVICE? CLARIFY. THIS DETAIL DOES
 NOT SHOW US HOW SPILLAGE WILL BE CONTROLLED. PLEASE
 CLARIFY PER WPB AMEND. TO FBC 107.2.1
  
 5. PREVIOUS COMMENT 18) SUBMIT A CONDENSATE RISER FOR
 REVIEW. SHOW THE TERMINATION POINT OF THE CONDENSATE
 DRAINS. FBC 107.1. YOU RESPONDED THAT A RISER WAS ADDED
 BUT COULD NOT FIND IT PLEASE CLARIFY.
  
 6. SHT. P0.03 DETAIL FOR WATER HEATER. THE RETURN LINE
 OF THE RECIRCULATION SYSTEM SHALL SHOW THAT IT CONNECTS
 TO BOTH THE COLD INLET OF THE WATER HEATER AND THE COLD
 WATER INLET OF THE THERMOSTATIC MIXING VALVE . PER FBC
 PL SEC. 607.2.2
  
 7. SHT. P1.04+P3.03 SNK 1+2 SHALL BE PROVIDE WITH HOT
 OR TEMPERED WATER. PER FBC PL 607.1
  
 8. SHT. P3.02 SHOW WATER HAMMER ARRESTOR ON ICE
 MACHINE. PER FBC PL 604.9
  
 9. PLEASE SHOW FLOW ARROWS ON HOT WATER RETURN SYSTEM .
 PER WPB AMEND TO FBC 107.2.1
  
  