Date |
Text |
2016-05-17 15:20:15 | 1) SUBMIT THE OCCUPANT LOAD FOR THE A-3 OCCUPANCY AND |
| ALSO FOR THE B OCCUPANCY.FBC 1004.1. |
| 2) SHT. AE 410 - SHOW THE REQUIRED CLEAR FLOOR SPACE |
| FOR THE BREAK ROOM SINK. 2014 FBC-ACCESSIBILITY |
| SEC.606.2. |
| 3) SHT. AE 401 - CLEARLY SHOW THE INSIDE CLEAR |
| DIMENSIONS OF THE ACCESSIBLE SHOWERS. TRANSFER SHOWERS |
| SHALL BE 36 INCHES BY 36 INCHES CLEAR INSIDE DIMENSIONS |
| PER 2014 FAC SEC.608.2.1. |
| 4) SHT.AE 403 - TOILET ACCESSORY LEGEND - NOTE # 4 |
| REFERS TO CHAPTER 11 SEC. 4.1.3 OF ADA. REVISE NOTE TO |
| READ 2014 FBC-ACCESSIBILITY. THERE IS NO CHAPTER 11 |
| SEC. 4.1.3. IN THE 2014 FL. ACCESS. CODE. |
| 5) SHT. AE 911 - THE GRAB BARS SHALL BE MEASURED TO THE |
| TOP OF THE GRIPPING SURFACE, NOT TO THE CENTER AS |
| SHOWN. 2014 FAC SEC. 609.4. |
| 6) INDICATE THE ACCESSIBLE URINAL IN EACH MEN'S |
| RESTROOM ON THE FLOOR PLANS AND ON THE ELEVATION |
| DRAWINGS. SHOW THE REQUIRED CLEAR FLOOR SPACE ON THE |
| PLANS. COMPLY WITH 2014 FAC SEC.605.1 THRU 605.4. |
| 7) SHOW THE INSIDE CLEAR DIMENSIONS (LXW) OF ALL |
| ACCESSIBLE TOILET COMPARTMENTS AND TOILET ROOMS ON THE |
| PLAN. FBC 107.2.1. |
| 8) SHOW THE LENGTH AND WIDTH OF THE STANDARD TOILET |
| STALLS ON THE PLAN. COMPLY WITH 2014 FPC SEC. 405.3.1. |
| 9) AT LEAST ONE LAVATORY LOCATED OUTSIDE OF THE TOILET |
| COMPARTMENT IN THE RESTROOMS SHALL COMPLY WITH FAC |
| SEC.213.3.4. |
| 10) SHT. AE 911 - THE TOP OF THE SHOWER SEAT SHALL BE A |
| MAXIMUM OF 19 INCHES ABOVE THE FINISHED FLOOR.FAC |
| SEC.610.3. |
| 11) SHT. AE 911 - THE MAXIMUM SPOUT HEIGHT OF THE |
| DRINKING FOUNTAIN FOR PERSONS IN A WHEELCHAIR SHALL BE |
| A MAXIMUM OF 36 INCHES. THE SPOUT HEIGHT OF THE |
| DRINKING FOUNTAIN FOR STANDING PERSONS SHALL BE 38 |
| INCHES MINIMUM AND 43 INCHES MAXIMUM ABOVE THE FINISH |
| FLOOR. FAC SECS.602.5 AND 602.7. |
| 12) SHOW THE REQUIRED TURNING SPACE IN THE TOILET ROOMS |
| & TOILET COMPARTMENTS.FAC SEC. 304. |
| 13) SHT. AE 801 - DETAIL #6 - SHOW THE REQUIRED KNEE |
| AND TOE CLEARANCES PER THE FAC SEC.306. |
| 14) SHT. AE 911 - THE TOILET PAPER DISPENSER SHALL BE |
| LOCATED 7"- 9" MAXIMUM IN FRONT OF THE WATER CLOEST TO |
| THE CENTERLINE OF THE DISPENSER PER FAC SEC. 604.7. |
| 15) THE SHOWER CONTROLS SHALL BE LOCATED A MAXIMUM 15 |
| INCHES FROM THE CENTERLINE OF THE SEAT TOWARD THE |
| SHOWER OPENING.INDICATE THIS ON THE PLAN. FAC |
| SEC.608.5.1. |
| 16) SHT. P0.03 - SUBMIT MANUFACTURER'S SPECIFICATIONS |
| FOR THE OIL GUARD SUMP PUMP SYSTEM. FPC SEC.1003.4 - |
| EXCEPTION. |
| 17) SHT.P0.03 - CONDENSATE BOX DETAIL - HOW WILL THE |
| POSSIBILITY OF WATER SPILLAGE BE CONTROLLED WITH THIS |
| DEVICE? CLARIFY. |
| 18) SUBMIT A CONDENSATE RISER FOR REVIEW. SHOW THE |
| TERMINATION POINT OF THE CONDENSATE DRAINS. FBC 107.1. |
| 19)SHT. P0.03 - WATER HEATER DETAIL SHOWS THE WATER |
| HEATERS AS BEING BOTTOM FED & THE WATER RISER ON SHT. |
| P3.03 SHOWS THE WATER HEATERS AS TOP FED. CLARIFY. |
| BOTTOM FED WATER HEATERS SHALL BE EQUIPPED WITH A |
| VACUUM RELIEF ON THE CCOLD WATER SUPPLY PER FPC |
| SEC.504.2. |
| 20) SHT. P0.03 - WATER HEATER DETAIL - THE HOT WATER |
| RETURN LINE SHALL ALSO CONNECT TO THE COLD WATER INLET |
| TO THE WATER HEATERS. THE FLOW ARROW ON THE DETAIL DOES |
| NOT SEEM TO MEET THE INTENT OF FPC 607.2.1. |
| 21) SHT.P3.04 - INDICATE THE SLOPE OF THE HORIZONTAL |
| STORM DRAIN PIPING. SIZING SHALL COMPLY WITH FPC TABLE |
| 1106.3. THE DESIGN OF THE STORM DRAIN SYSTEM SHALL |
| INCLUDE 1/2 THE AREA OF ANY VERTICAL WALL THAT DIVERTS |
| RAINWATER TO THE ROOF. SUBMIT CALCULATIONS. |
| 22) SHT. P3.04 - RISER 3 ST - SIZE THE HORIZONTAL LINE |
| DRAINING 2480 SQ. FT., 6115 SQ. FT., & 1835 SQ. FT. THE |
| STORM DRAIN SYSTEM SHALL BE SIZED ON A RAINFALL RATE OF |
| 5 INCHES PER HOUR. |
| 23) SHT. P3.04 - RISER 2 ST - THE 6" LINE DRAINING 5185 |
| SQ. FT. MAY BE UNDERSIZED.INDICATE THE PIPE SLOPE AND |
| COMPLY WITH FPC TABLE 1106.3. |
| 24) A BACKFLOW PREVENTER IS REQUIRED ON THE WATER |
| SUPPLY TO THE REFRIGERATOR FOR THE ICE MAKER AND A |
| WATER HAMMER ARRESTOR IS REQUIRED BECAUSE IT IS A QUICK |
| CLOSING VALVE. FPC SEC.608.3. |
| 25) SHT. P3.01 - SIZE ALL SECTIONS OF THE VENTS AND THE |
| WASTE STACKS. THERE ARE NUMEROUS SECTIONS THAT ARE NOT |
| SIZED. FBC 107.2.1. |
| 26) SHT. P3.01 - THE SH-2 SHOWERS IN MEN'S RESTROOM |
| 158B & 159B AS DRAWN ON THE RISER CREATE A PLUMBING |
| CODE VIOLATION FOR FIXTURES PERMITTED ON A WET VENT. |
| EITHER INDIVIDUALLY VENT EACH SHOWER OR CONNECT BOTH |
| SHOWERS TO THE STACK.FPC SEC. 912. |
| 27) THE SHOWERS IN ROOMS 148B & 153B AS DRAWN ON THE |
| RISER CREATE A PLUMBING CODE VIOLATION OF FPC SEC. 912 |
| FOR THE NUMBER AND TYPE OF FIXTURE PERMITTED ON A WET |
| VENT. |
| 28) THE VENT FOR THE MOP SINK AND THE FLOOR DRAIN SHALL |
| BE LOCATED BETWWEEN THE TWO FIXTURES. FPC SECS.901.2, |
| 901.2.1. |
| 29) SHT. P3.01 - THE VENT FOR THE STATIONARY WHIRLPOOLS |
| SHALL BE LOCATED BETWEEN THE TWO DRAINS. FPC SECS. |
| 901.2, 901.2.1. |
| 30) CLEANOUTS ARE REQUIRED IN THE BASE OF EACH SOIL OR |
| WASTE STACK. FPC SEC.708.3.4. |
| 31) INDICATE THE SLOPE OF THE BUILDING DRAIN AND |
| BRANCHES ON THE PLANS. COMPLY WITH FPC SEC.710 AND |
| TABLE 710.1 (1). |
| 32) THE WASHERS AND DRYERS SHALL COMPLY WITH |
| FBC-ACCESSIBILITY SEC.611. |
| 33) SIZE ALL SECTIONS OF THE WATER RISER.FBC 107.2.1. |
| 34) SHOW THE HOT WATER RECIRCULATING LINE ON SHEET |
| P3.02. |
| 35) SHT.P1.01 & P1.03 - RESTROOMS #155A & 156A - THE |
| RESTROOMS ARE MISLABELED. THE MEN'S IS SHOWN AS THE |
| WOMEN'S AND THE WOMEN'S IS SHOWN AS THE MEN'S. PLEASE |
| CORRECT. |
| 36) INDICATE THE ACCESSIBLE URINAL IN EACH MEN'S |
| RESTROOM ON THE FLOOR PLANS AND ON THE ELEVATION |
| DRAWINGS. SHOW THE REQUIRED CLEAR FLOOR SPACE ON THE |
| PLANS. COMPLY WITH 2014 FAC SEC.605.1 THRU 605.4. |
| 37) URINAL PARTITIONS SHALL COMPLY WITH 2014 FBC |
| SEC.1210.3.2. |
| 38) SUBMIT A DESIGN DETAIL FOR THE LINT TRAP / |
| INTERCEPTOR. COMPLY WITH 2014 FPC SEC.1003.6. |
| 39) SUBMIT MANUFACTURER'S INSTALLATION SPECIFICATIONS |
| FOR THE WHIRLPOOL TUBS. FBC 107.1. |
| |
| PLUMBING PLAN REVIEW |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| 561-805-6692 |
| [email protected] |
| |
| |
| |
| |