Plan Review Notes
Plan Review Notes For Permit 16050249
Permit Number 16050249
Review Stop P
Sequence Number 1
Notes
Date Text
2016-05-17 15:20:151) SUBMIT THE OCCUPANT LOAD FOR THE A-3 OCCUPANCY AND
 ALSO FOR THE B OCCUPANCY.FBC 1004.1.
 2) SHT. AE 410 - SHOW THE REQUIRED CLEAR FLOOR SPACE
 FOR THE BREAK ROOM SINK. 2014 FBC-ACCESSIBILITY
 SEC.606.2.
 3) SHT. AE 401 - CLEARLY SHOW THE INSIDE CLEAR
 DIMENSIONS OF THE ACCESSIBLE SHOWERS. TRANSFER SHOWERS
 SHALL BE 36 INCHES BY 36 INCHES CLEAR INSIDE DIMENSIONS
 PER 2014 FAC SEC.608.2.1.
 4) SHT.AE 403 - TOILET ACCESSORY LEGEND - NOTE # 4
 REFERS TO CHAPTER 11 SEC. 4.1.3 OF ADA. REVISE NOTE TO
 READ 2014 FBC-ACCESSIBILITY. THERE IS NO CHAPTER 11
 SEC. 4.1.3. IN THE 2014 FL. ACCESS. CODE.
 5) SHT. AE 911 - THE GRAB BARS SHALL BE MEASURED TO THE
 TOP OF THE GRIPPING SURFACE, NOT TO THE CENTER AS
 SHOWN. 2014 FAC SEC. 609.4.
 6) INDICATE THE ACCESSIBLE URINAL IN EACH MEN'S
 RESTROOM ON THE FLOOR PLANS AND ON THE ELEVATION
 DRAWINGS. SHOW THE REQUIRED CLEAR FLOOR SPACE ON THE
 PLANS. COMPLY WITH 2014 FAC SEC.605.1 THRU 605.4.
 7) SHOW THE INSIDE CLEAR DIMENSIONS (LXW) OF ALL
 ACCESSIBLE TOILET COMPARTMENTS AND TOILET ROOMS ON THE
 PLAN. FBC 107.2.1.
 8) SHOW THE LENGTH AND WIDTH OF THE STANDARD TOILET
 STALLS ON THE PLAN. COMPLY WITH 2014 FPC SEC. 405.3.1.
 9) AT LEAST ONE LAVATORY LOCATED OUTSIDE OF THE TOILET
 COMPARTMENT IN THE RESTROOMS SHALL COMPLY WITH FAC
 SEC.213.3.4.
 10) SHT. AE 911 - THE TOP OF THE SHOWER SEAT SHALL BE A
 MAXIMUM OF 19 INCHES ABOVE THE FINISHED FLOOR.FAC
 SEC.610.3.
 11) SHT. AE 911 - THE MAXIMUM SPOUT HEIGHT OF THE
 DRINKING FOUNTAIN FOR PERSONS IN A WHEELCHAIR SHALL BE
 A MAXIMUM OF 36 INCHES. THE SPOUT HEIGHT OF THE
 DRINKING FOUNTAIN FOR STANDING PERSONS SHALL BE 38
 INCHES MINIMUM AND 43 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR. FAC SECS.602.5 AND 602.7.
 12) SHOW THE REQUIRED TURNING SPACE IN THE TOILET ROOMS
 & TOILET COMPARTMENTS.FAC SEC. 304.
 13) SHT. AE 801 - DETAIL #6 - SHOW THE REQUIRED KNEE
 AND TOE CLEARANCES PER THE FAC SEC.306.
 14) SHT. AE 911 - THE TOILET PAPER DISPENSER SHALL BE
 LOCATED 7"- 9" MAXIMUM IN FRONT OF THE WATER CLOEST TO
 THE CENTERLINE OF THE DISPENSER PER FAC SEC. 604.7.
 15) THE SHOWER CONTROLS SHALL BE LOCATED A MAXIMUM 15
 INCHES FROM THE CENTERLINE OF THE SEAT TOWARD THE
 SHOWER OPENING.INDICATE THIS ON THE PLAN. FAC
 SEC.608.5.1.
 16) SHT. P0.03 - SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE OIL GUARD SUMP PUMP SYSTEM. FPC SEC.1003.4 -
 EXCEPTION.
 17) SHT.P0.03 - CONDENSATE BOX DETAIL - HOW WILL THE
 POSSIBILITY OF WATER SPILLAGE BE CONTROLLED WITH THIS
 DEVICE? CLARIFY.
 18) SUBMIT A CONDENSATE RISER FOR REVIEW. SHOW THE
 TERMINATION POINT OF THE CONDENSATE DRAINS. FBC 107.1.
 19)SHT. P0.03 - WATER HEATER DETAIL SHOWS THE WATER
 HEATERS AS BEING BOTTOM FED & THE WATER RISER ON SHT.
 P3.03 SHOWS THE WATER HEATERS AS TOP FED. CLARIFY.
 BOTTOM FED WATER HEATERS SHALL BE EQUIPPED WITH A
 VACUUM RELIEF ON THE CCOLD WATER SUPPLY PER FPC
 SEC.504.2.
 20) SHT. P0.03 - WATER HEATER DETAIL - THE HOT WATER
 RETURN LINE SHALL ALSO CONNECT TO THE COLD WATER INLET
 TO THE WATER HEATERS. THE FLOW ARROW ON THE DETAIL DOES
 NOT SEEM TO MEET THE INTENT OF FPC 607.2.1.
 21) SHT.P3.04 - INDICATE THE SLOPE OF THE HORIZONTAL
 STORM DRAIN PIPING. SIZING SHALL COMPLY WITH FPC TABLE
 1106.3. THE DESIGN OF THE STORM DRAIN SYSTEM SHALL
 INCLUDE 1/2 THE AREA OF ANY VERTICAL WALL THAT DIVERTS
 RAINWATER TO THE ROOF. SUBMIT CALCULATIONS.
 22) SHT. P3.04 - RISER 3 ST - SIZE THE HORIZONTAL LINE
 DRAINING 2480 SQ. FT., 6115 SQ. FT., & 1835 SQ. FT. THE
 STORM DRAIN SYSTEM SHALL BE SIZED ON A RAINFALL RATE OF
 5 INCHES PER HOUR.
 23) SHT. P3.04 - RISER 2 ST - THE 6" LINE DRAINING 5185
 SQ. FT. MAY BE UNDERSIZED.INDICATE THE PIPE SLOPE AND
 COMPLY WITH FPC TABLE 1106.3.
 24) A BACKFLOW PREVENTER IS REQUIRED ON THE WATER
 SUPPLY TO THE REFRIGERATOR FOR THE ICE MAKER AND A
 WATER HAMMER ARRESTOR IS REQUIRED BECAUSE IT IS A QUICK
 CLOSING VALVE. FPC SEC.608.3.
 25) SHT. P3.01 - SIZE ALL SECTIONS OF THE VENTS AND THE
 WASTE STACKS. THERE ARE NUMEROUS SECTIONS THAT ARE NOT
 SIZED. FBC 107.2.1.
 26) SHT. P3.01 - THE SH-2 SHOWERS IN MEN'S RESTROOM
 158B & 159B AS DRAWN ON THE RISER CREATE A PLUMBING
 CODE VIOLATION FOR FIXTURES PERMITTED ON A WET VENT.
 EITHER INDIVIDUALLY VENT EACH SHOWER OR CONNECT BOTH
 SHOWERS TO THE STACK.FPC SEC. 912.
 27) THE SHOWERS IN ROOMS 148B & 153B AS DRAWN ON THE
 RISER CREATE A PLUMBING CODE VIOLATION OF FPC SEC. 912
 FOR THE NUMBER AND TYPE OF FIXTURE PERMITTED ON A WET
 VENT.
 28) THE VENT FOR THE MOP SINK AND THE FLOOR DRAIN SHALL
 BE LOCATED BETWWEEN THE TWO FIXTURES. FPC SECS.901.2,
 901.2.1.
 29) SHT. P3.01 - THE VENT FOR THE STATIONARY WHIRLPOOLS
 SHALL BE LOCATED BETWEEN THE TWO DRAINS. FPC SECS.
 901.2, 901.2.1.
 30) CLEANOUTS ARE REQUIRED IN THE BASE OF EACH SOIL OR
 WASTE STACK. FPC SEC.708.3.4.
 31) INDICATE THE SLOPE OF THE BUILDING DRAIN AND
 BRANCHES ON THE PLANS. COMPLY WITH FPC SEC.710 AND
 TABLE 710.1 (1).
 32) THE WASHERS AND DRYERS SHALL COMPLY WITH
 FBC-ACCESSIBILITY SEC.611.
 33) SIZE ALL SECTIONS OF THE WATER RISER.FBC 107.2.1.
 34) SHOW THE HOT WATER RECIRCULATING LINE ON SHEET
 P3.02.
 35) SHT.P1.01 & P1.03 - RESTROOMS #155A & 156A - THE
 RESTROOMS ARE MISLABELED. THE MEN'S IS SHOWN AS THE
 WOMEN'S AND THE WOMEN'S IS SHOWN AS THE MEN'S. PLEASE
 CORRECT.
 36) INDICATE THE ACCESSIBLE URINAL IN EACH MEN'S
 RESTROOM ON THE FLOOR PLANS AND ON THE ELEVATION
 DRAWINGS. SHOW THE REQUIRED CLEAR FLOOR SPACE ON THE
 PLANS. COMPLY WITH 2014 FAC SEC.605.1 THRU 605.4.
 37) URINAL PARTITIONS SHALL COMPLY WITH 2014 FBC
 SEC.1210.3.2.
 38) SUBMIT A DESIGN DETAIL FOR THE LINT TRAP /
 INTERCEPTOR. COMPLY WITH 2014 FPC SEC.1003.6.
 39) SUBMIT MANUFACTURER'S INSTALLATION SPECIFICATIONS
 FOR THE WHIRLPOOL TUBS. FBC 107.1.
  
 PLUMBING PLAN REVIEW