Plan Review Notes
Plan Review Notes For Permit 16050249
Permit Number 16050249
Review Stop M
Sequence Number 1
Notes
Date Text
2016-05-17 08:08:411ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16050249
 5/17/16
  
 1) PROVIDE EXHAUST VENTILATION CALCULATIONS FOR THE
 LOCKER ROOMS AND BATH ROOMS, AND PROVIDE HVAC CONTROL
 SEQUENCING DETAILS- SEE TABLE 403.3 FBC-14 MECHANICAL
 AND ASHRAE 62.1-2010.
  
 2) SHEET M0.02: REFER TO TABLE D-1 ASHRAE 90.1 AND
 CORRECT THE DRY AND WET BULB TEMPERATURES FOR WEST PALM
 BEACH SHOWN ON THE PLAN AND IN THE AC CALCULATIONS.
  
 3) SUBMIT A 2ND SET OF ENERGY AND AC CALCULATIONS, AND
 COMPLETE THE MANDATORY REQUIREMENTS CHECKLIST ON PAGE
 11 OF THE ENERGY SUBMITTAL.
  
 4) SHEETS M1.01, M1.02, & M1.03: PLEASE LABEL THE O/A
 INTAKES A) PROVIDE SHUTOFF DAMPER CONTROLS FOR THE O/A
 AND EXHAUST DUCTS.- SECTION C403.2.4.4 FBC-14 ENERGY
 CONSERVATION. B) VERIFY COMPLIANCE WITH SECTIONS 401.4
 AND 501.3.1 FBC-14 MECHANICAL - REQUIRED CLEARANCES FOR
 O/A INTAKES AND EXHAUST OUTLETS. C) INDICATE HOW THE
 O/A INLET AND EXHAUST OUTLET OPENINGS WILL PROTECTED IN
 COMPLIANCE WITH SECTIONS 401.5 AND 501.3.2 , AND
 PROVIDE SUBMITTALS APPROVED WITH SIGNATURE BY THE
 DESIGN PROFESSIONAL.
  
 5) M1.01, M1.02, M1.03: PROVIDE DUCT SMOKE DETECTORS IN
 THE RETURN AIR SYSTEMS OF ALL SYSTEMS RETURNING OVER
 2000 CFM'S- SECTION 606.2.1. INDICATE CONTROLS
 OPERATION AND SUPERVISION OF THE DETECTORS, AND PROVIDE
 A SUBMITTAL APPROVED WITH SIGNATURE BY THE DESIGN
 PROFESSIONAL,
  
 6) M1.01 & M1.02: AHU-4 SHALL NOT SUPPLY AIR TO STAIR
 #1- REFER TO SECTION 1022.6 FBC-14 BUILDING: THE
 INTERIOR EXIT STAIRWAY AND RAMP VENTILATION SYSTEMS
 SHALL BE INDEPENDENT OF OTHER BUILDING VENTILATION
 SYSTEMS.
  
 7) M1.01: PROVIDE AN INDEPENDENT EXHAUST SYSTEM FOR THE
 JANITOR ROOM- SECTION 501.2.
  
 8) M1.01, LAUNDRY ROOM: SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE DRYERS WITH APPROVAL SIGNATURE
 BY THE DESIGN PROFESSIONAL- REFER TO SECTION 504.7 AND
 REVISE THE PLAN TO SHOW COMPLIANCE.
 504.7 COMMERCIAL CLOTHES DRYERS.
 THE INSTALLATION OF DRYER EXHAUST DUCTS SERVING
 COMMERCIAL CLOTHES DRYERS SHALL COMPLY WITH THE
 APPLIANCE MANUFACTURER'S INSTALLATION INSTRUCTIONS.
 EXHAUST FAN MOTORS INSTALLED IN EXHAUST SYSTEMS SHALL
 BE LOCATED OUTSIDE OF THE AIRSTREAM. IN MULTIPLE
 INSTALLATIONS, THE FAN SHALL OPERATE CONTINUOUSLY OR BE
 INTERLOCKED TO OPERATE WHEN ANY INDIVIDUAL UNIT IS
 OPERATING. DUCTS SHALL HAVE A MINIMUM CLEARANCE OF 6
 INCHES (152 MM) TO COMBUSTIBLE MATERIALS. CLOTHES DRYER
 TRANSITION DUCTS USED TO CONNECT THE APPLIANCE TO THE
 EXHAUST DUCT SYSTEM SHALL BE LIMITED TO SINGLE LENGTHS
 NOT TO EXCEED 8 FEET (2438 MM) IN LENGTH AND SHALL BE
 LISTED AND LABELED FOR THE APPLICATION. TRANSITION
 DUCTS SHALL NOT BE CONCEALED WITHIN CONSTRUCTION.
 A) INDICATE THE GAGE OF THE DRYER EXHAUST DUCT. B)
 INDICATE HOW MAKE-UP MAIR IS BEING RPOVIDE AND PROVIDE
 A CALCULATION.
  
 9) M1.03: THE LABEL FOR AHU-4 IS MISSING.
  
 10) M3.01: PROVIDE THE WIND LOAD DESIGN CRITERIA ON THE
 PLAN- SECTION 301.15 FBC-14 MECHANICAL.
  
 11) INDICATE HOW ACC/AHU-6 WAS SIZED- PROVIDE A
 CALCULATION.
  
 12) M0.02: A) PROVIDE THE CORRECT SPELLING FOR
 "CONDENSER" IN THE SCHEDULE. B) PROVIDE THE EFFICIENCY
 RATINGS FOR THE ACC SYSTEMS 1-5 IN THE SCHEDULE.
  
 13) PROVIDE CONDENSATE DISPOSAL PLANS FOR ALL SYSTEMS-
 SECTION 307.
  
 14) REFER TO SECTION C403.2.7.2 FBC-14 ENERGY
 CONSERVATION AND PROVIDE CONSTRUCTION DETAILS AND
 MATERIALS COMPLIANCE FOR THE MECHANICAL CLOSETS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  