2016-05-09 15:25:00THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET LS 101 - STAIR 1 INDICATES ITS EXIT TO THE
 INTERIOR OB THE BUILDING. THE EXIT DOES NOT MEET THE
 REQUIREMENTS BELOW # 1, 136 OCCUPANTS VS 105 FOR STAIR
 # 2. AND # 3 THE EXIT PATH IS READILY VISIBLE AND
 IDENTIFIABLE.
  
 AN EXTERIOR EXIT DOOR IS REQUIRED IN STAIR # 1.
  
 PER NFPA 101, CHAPTER 12, NEW ASSEMBLY OCCUPANCIES,
 12.2.7 DISCHARGE FROM EXITS.
 12.2.7.1 EXIT DISCHARGE SHALL COMPLY WITH SECTION 7.7.
  
 7.7 DISCHARGE FROM EXITS.
 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE
 DIRECTLY, AT A PUBLIC WAY OR AT AN EXTERIOR EXIT
 DISCHARGE, UNLESS OTHERWISE PROVIDED IN 7.7.1.2 THROUGH
 7.7.1.4.
 7.7.2 EXIT DISCHARGE THROUGH INTERIOR BUILDING AREAS.
 EXITS SHALL BE PERMITTED TO DISCHARGE THROUGH INTERIOR
 BUILDING AREAS, PROVIDED THAT ALL OF THE FOLLOWING ARE
 MET:
 (1) NOT MORE THAN 50 PERCENT OF THE REQUIRED NUMBER OF
 EXITS, AND NOT MORE THAN 50 PERCENT OF THE REQUIRED
 EGRESS CAPACITY, SHALL DISCHARGE THROUGH AREAS ON ANY
 LEVEL OF DISCHARGE, EXCEPT AS OTHERWISE PERMITTED BY
 ONE OF THE FOLLOWING:
 (A) ONE HUNDRED PERCENT OF THE EXITS SHALL BE PERMITTED
 TO DISCHARGE THROUGH AREAS ON ANY LEVEL OF DISCHARGE IN
 DETENTION AND CORRECTIONAL OCCUPANCIES AS OTHERWISE
 PROVIDED IN CHAPTERS 22 AND 23.
 (B) IN EXISTING BUILDINGS, THE 50 PERCENT LIMIT ON
 EGRESS CAPACITY SHALL NOT APPLY IF THE 50 PERCENT LIMIT
 ON THE REQUIRED NUMBER OF EXITS IS MET.
 (2) EACH LEVEL OF DISCHARGE SHALL DISCHARGE DIRECTLY
 OUTSIDE AT THE FINISHED GROUND LEVEL OR DISCHARGE
 DIRECTLY OUTSIDE AND PROVIDE ACCESS TO THE FINISHED
 GROUND LEVEL BY OUTSIDE STAIRS OR OUTSIDE RAMPS.
 (3) THE INTERIOR EXIT DISCHARGE SHALL LEAD TO A FREE
 AND UNOBSTRUCTED WAY TO THE EXTERIOR OF THE BUILDING,
 AND SUCHWAY SHALL BE READILY VISIBLE AND IDENTIFIABLE
 FROM THE POINT OF DISCHARGE FROM THE EXIT.
 (4) THE INTERIOR EXIT DISCHARGE SHALL BE PROTECTED BY
 ONE OF THE FOLLOWING METHODS:
 (A) THE LEVEL OF DISCHARGE SHALL BE PROTECTED
 THROUGHOUT BY AN APPROVED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 9.7, OR THE PORTION OF THE
 LEVEL OF DISCHARGE USED FOR INTERIOR EXIT DISCHARGE
 SHALL BE PROTECTED BY AN APPROVED AUTOMATIC SPRINKLER
 SYSTEM IN ACCORDANCE WITH SECTION 9.7 AND SHALL BE
 SEPARATED FROM THE NONSPRINKLERED PORTION OF THE FLOOR
 BY FIRE BARRIERS WITH A FIRE RESISTANCE RATING MEETING
 THE REQUIREMENTS FOR THE ENCLOSURE OF EXITS. (SEE
 7.1.3.2.1.)
 (B) THE INTERIOR EXIT DISCHARGE AREA SHALL BE IN A
 VESTIBULE OR FOYER THAT MEETS ALL OF THE FOLLOWING
 CRITERIA:
 I. THE DEPTH FROM THE EXTERIOR OF THE BUILDING SHALL BE
 NOT MORE THAN 10 FT (3050 MM), AND THE LENGTH SHALL BE
 NOT MORE THAN 30 FT (9.1 M).
 II. THE FOYER SHALL BE SEPARATED FROM THE REMAINDER OF
 THE LEVEL OF DISCHARGE BY CONSTRUCTION PROVIDING
 PROTECTION NOT LESS THAN THE EQUIVALENT OF WIRED GLASS
 IN STEEL FRAMES OR 45 MINUTES FIRERESISTIVE
 CONSTRUCTION.
 III. THE FOYER SHALL SERVE ONLY AS MEANS OF EGRESS AND
 SHALL INCLUDE AN EXIT DIRECTLY TO THE OUTSIDE.
 (5) THE ENTIRE AREA ON THE LEVEL OF DISCHARGE SHALL BE
 SEPARATED FROM AREAS BELOW BY CONSTRUCTION HAVING A
 FIRE RESISTANCE RATING NOT LESS THAN THAT REQUIRED FOR
 THE EXIT ENCLOSURE, UNLESS OTHERWISE PROVIDED IN
 7.7.2(6).
 (6) LEVELS BELOW THE LEVEL OF DISCHARGE IN AN ATRIUM
 SHALL BE PERMITTED TO BE OPEN TO THE LEVEL OF DISCHARGE
 WHERE SUCH LEVEL OF DISCHARGE IS PROTECTED IN
 ACCORDANCE WITH 8.6.7.
  
 2) SHEET FA 1.01 - PLEASE PROVIDE A NOTE INDICATING
 THAT THE FIRE ALARM WORK SHALL BE SUBMITTED AND
 COMPLETED UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED
 LIFE SAFETY CONTRACTOR.
  
 3) SHEET M 0.02 - DUCT DETECTORS ARE NOT CLEARLY
 INDICATED OR COULD BE EASILY LOCATED. PER NFPA CHAPTER
 12, 12.5 BUILDING SERVICES.
 12.5.1 UTILITIES. UTILITIES SHALL COMPLY WITH THE
 PROVISIONS OF SECTION 9.1.
 12.5.2 HEATING, VENTILATING, AND AIR-CONDITIONING
 EQUIPMENT. HEATING, VENTILATING, AND AIR-CONDITIONING
 EQUIPMENT SHALL COMPLY WITH THE PROVISIONS OF SECTION
 9.2.
  
 9.2 HEATING, VENTILATING, AND AIR-CONDITIONING.
 9.2.1 AIR-CONDITIONING, HEATING, VENTILATING DUCTWORK,
 AND RELATED EQUIPMENT. AIR-CONDITIONING, HEATING,
 VENTILATING DUCTWORK, AND RELATED EQUIPMENT SHALL BE IN
 ACCORDANCE WITH NFPA 90A, STANDARD FOR THE INSTALLATION
 OF AIR-CONDITIONING AND
 VENTILATING SYSTEMS, OR NFPA 90B, STANDARD FOR THE
 INSTALLATION OF WARM AIR HEATING AND AIR-CONDITIONING
 SYSTEMS, AS APPLICABLE, UNLESS SUCH INSTALLATIONS ARE
 APPROVED EXISTING INSTALLATIONS, WHICH SHALL BE
 PERMITTED TO BE CONTINUED IN SERVICE.
  
 PER NFPA 90 A , CHAPTER 6 CONTROLS
 6.4* SMOKE DETECTION FOR AUTOMATIC CONTROL.
 6.4.1 TESTING. ALL AUTOMATIC SHUTDOWN DEVICES SHALL BE
 TESTEDAT LEAST ANNUALLY.
 6.4.2* LOCATION.
 6.4.2.1 SMOKE DETECTORS LISTED FOR USE IN AIR
 DISTRIBUTION SYSTEMS SHALL BE LOCATED AS FOLLOWS:
 (1) DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY
 BRANCH CONNECTIONS IN AIR SUPPLY SYSTEMS HAVING A
 CAPACITY GREATER THAN 944 L/SEC (2000 FT3/MIN)
 (2) AT EACH STORY PRIOR TO THE CONNECTION TO A COMMON
 RETURN AND PRIOR TO ANY RECIRCULATION OR FRESH AIR
 INLET CONNECTION IN AIR RETURN SYSTEMS HAVING A
 CAPACITY GREATER THAN 7080 L/SEC (15,000 FT3/MIN) AND
 SERVING MORE THAN ONE STORY
  
 3) SHEET AE701 - THE DOOR & FRAME SCHEDULE DOES NOT
 INDICATE ANY DOOR HARDWARE SPECIFCALLY, EXIT DOOR
 HARDWARE AND PANIC DEVICES. PLEASE PROVIDE DETAIL
 HARDWARE DEVICES FOR EACH DOOR PER NFPA 101 CHAPTER 12,
 12.2.2.2 DOORS
 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS
 SHALL BE PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK
 ONLY IF THE LATCH OR LOCK IS PANIC HARDWARE OR FIRE
 EXIT HARDWARE COMPLYING WITH 7.2.1.7, UNLESS OTHERWISE
 PERMITTED BY ONE OF THE FOLLOWING:
 (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS
 LOCKS AS PERMITTED IN 12.2.2.2.5.
 (2) THIS REQUIREMENT SHALL NOT APPLY TO
 ACCESS-CONTROLLED EGRESS DOORS AS PERMITTED IN
 12.2.2.2.6.
  
 4) SHEET AE 210 - THERE IS NO INDICATION OF A LIGHT
 WEIGHT ROOF AND/OR FLOOR SIGN PLEASE PROVIDE FOR A
 LIGHTWEIGHT SIGN PER FLORIDA 69A-60.0081; NOTICE
 SIGNAGE IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR
 ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR
 MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH A MALTESE CROSS SIGN MEASURING 8 INCHES
 HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED
 REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED
 WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR.
 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
 5) SHEET AE 112 - THERE IS NO INDICATION OF THE
 DIMENSIONS OF CORRIDORS 130 AND 133. PLEASE PROVIE THE
 DIMENSIONS COMPLY WITH NFPA 101, CHAPTER 12, 12.2.3.8
 MINIMUM CORRIDOR WIDTH. THE WIDTH OF ANY EXIT ACCESS
 CORRIDOR SERVING 50 OR MORE PERSONS SHALL BE NOT LESS
 THAN 44 IN. (1120 MM).
  
 PETER LEDUC
 FIRE MARSHAL