2016-06-06 11:34:42 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| GOVERNING CODE: FBC 5TH EDITION (FBC 2014) |
| |
| 1. FLORIDA STATUTE 553.71, IT APPEARS THAT THIS |
| BUILDING MAY QUALIFY AS A THRESHOLD BUILDING; ANY |
| BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN |
| HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY |
| CLASSIFICATION AS DEFINED IN THE FLORIDA BUILDING CODE |
| WHICH EXCEEDS 5,000 SF IN AREA AND AN OCCUPANT CONTENT |
| OF GREATER THAN 500 PERSONS. |
| |
| 2. AS A THRESHOLD BUILDING, THE FOLLOWING IS REQUIRED: |
| |
| A. THRESHOLD INSPECTION PLAN; FS 553.79(5)(A), CITY OF |
| WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION 109.3.6.1. THE |
| ENFORCING AGENCY SHALL REQUIRE A SPECIAL INSPECTOR TO |
| PERFORM STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING |
| PURSUANT TO A STRUCTURAL INSPECTION PLAN PREPARED BY |
| THE ENGINEER OR ARCHITECT OF RECORD. THE STRUCTURAL |
| INSPECTION PLAN MUST BE SUBMITTED TO AND APPROVED BY |
| THE ENFORCING AGENCY BEFORE THE ISSUANCE OF A BUILDING |
| PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. |
| THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO |
| PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO |
| THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR |
| COMPLIANCE WITH THE PERMITTED DOCUMENTS. |
| |
| B. THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD |
| BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FS |
| 553.79(5)(A) TO THE MINIMUM INSPECTIONS REQUIRED BY |
| THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED |
| TO BE FILED OUT BY ALL PARTIES, NOTARIZED AND RETURNED |
| TO THIS OFFICE, REVIEWED AND APPROVED PRIOR TO PERMIT |
| ISSUANCE. CONTACT KEN CONRAD, MANAGER OF THE SPECIAL |
| INSPECTOR PROGRAM, AT 561-805-6666 FOR ADDITIONAL |
| INFORMATION. |
| FORMS WERE SENT TO: [email protected] |
| ON 5/28/16. |
| |
| C. SPECIAL INSPECTOR RESUME': PROVIDE A RESUME' OF |
| INSPECTION EXPERIENCE ON PREVIOUS PROJECTS FOR REVIEW |
| BY THE BUILDING OFFICIAL OR HIS DESIGNEE. AFTER THE |
| RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED. |
| UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED |
| FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA. THE |
| RESUME' IS TO BE SUBMITTED TO KEN CONRAD (AND COPY |
| SAMANTHA HILL), 561-805-6666, [email protected], |
| [email protected] |
| |
| ALL PROSPECTIVE INSPECTORS ARE TO BE APPROVED BY THE |
| CHIEF BUILDING INSPECTOR AND ALL ARE REQUIRED TO SIGN |
| THE SPECIAL INSPECTOR AGREEMENT. |
| |
| D. CONTRACTOR RESUME': PROVIDE A JOB SUMMARY OR HISTORY |
| FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE SUBMITTED TO |
| KEN CONRAD, (PLEASE COPY SAMANTHA HILL) VIA E-MAIL |
| ([email protected], [email protected]). |
| |
| E. PERMIT DOCUMENTS: PAPER SUBMITTALS REQUIRE THREE |
| SIGNED AND SEALED (IF APPLICABLE) ORIGINAL SETS OF ALL |
| DOCUMENTS. |
| |
| F. THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. |
| AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH |
| ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE |
| PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| MINIMUM BUILDING CODES AND THE APPLICABLE FIRESAFETY |
| STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN |
| ACCORDANCE WITH THIS CHAPTER AND CHAPTER 633. |
| |
| I WAS UNABLE TO LOCATE THIS STATEMENT ON THE |
| ARCHITECT'S PLANS. |
| |
| THE ENGINEER HAS A SIMILAR STATEMENT BUT LACKS SOME OF |
| THE STATUTORY LANGUAGE; PLEASE REVISE. |
| |
| 3. ADVISORY ONLY; PER FS 553.79, ALL SHORING/RE-SHORE |
| ENGINEERING IS TO BE REVIEWED BY ENGINEER OF RECORD |
| AND THREE SIGNED AND SEALED ORIGINAL SETS ARE TO BE |
| SUBMITTED FOR PLAN REVIEW. THE SHORING/RESHORE |
| ENGINEERING IS TO BE REVIEWED AND APPROVED PRIOR TO |
| INSPECTION. THE CITY APPROVED (CITY STAMPED) |
| SHORING/RE-SHORE ENGINEERING IS TO BE AVAILABLE ON THE |
| JOB AT THE TIME OF INSPECTION. |
| |
| 4. ADVISORY ONLY; PRIOR TO INSTALLATION, A GUARD RAIL |
| DETAIL IS TO BE SUBMITTED FOR PLAN REVIEW. THIS SHOULD |
| BE SUBMITTED WITH THE SHORING/RESHORE ENGINEERING. |
| |
| 5. SEE IMPACT FEE REVIEW. |
| |
| 6. ADVISORY ONLY; SEE ROOF (R STOP) REVIEW. NO ROOFING |
| INFORMATION PROVIDED IF ROOFING INFORMATION (PRODUCT |
| APPROVAL REVIEWED BY DESIGNER OF RECORD, ASSEMBLY |
| PROPOSED, ENHANCED FASTENING CALCULATIONS IF REQUIRED) |
| IS NOT SUBMITTED PRIOR TO PERMIT ISSUANCE, THIS PERMIT |
| WILL BE ISSUED WITH PROVISO. ROOF INFORMATION WILL BE |
| REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED PRIOR |
| TO INSTALLATION. |
| |
| 7. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR |
| PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED |
| ORIGINALS. SHEETS C1 THROUGH C4 PREPARED BY RICHARD |
| REIKENIS, PE ARE COPIES. THESE PAGES LACK THE |
| CERTIFICATE OF AUTHORIZATION, REFERENCE AN OUTDATED |
| BUILDING CODE, AND THE SEAL LACKS A DATE. ALSO, PLEASE |
| NOTE THAT THIS ENGINEER HAS NOT YET COMPLIED WITH FS |
| 471.0195, FAC 61G15-22.01 (MANDATORY BY JUNE 30, 2016). |
| NOTE THAT THIS ENGINEER, ALTHOUGH RESPONSIBLE FOR CIVIL |
| SHEETS, HAS REFERENCED ACCESSIBILITY ON HIS PLAN. SEE |
| PAGE 4 OF THE APRIL EDITION OF THE FBPE NEWSLETTER FOR |
| MORE INFORMATION: |
| |
| HTTPS://WWW.FBPE.ORG/INDEX.PHP/FILE-DOWNLOADS/SEND/56- |
| 2015-2016-FBPE-NEWSLETTERS/377-APRIL-2016-FBPE-NEWSLET |
| TER |
| |
| 8. GENERAL ADVISORY TO ALL ENGINEERS WHO DESIGN |
| BUILDINGS, STRUCTURES, FACILITIES OR SYSTEMS COVERED BY |
| THE FLORIDA BUILDING CODE, ALL ENGINEERS ARE REQUIRED |
| TO COMPLETE THE ADVANCED BUILDING CODE COURSE BY JUNE |
| 30, 2016, FS471.0195 AND FAC61G15-22.001. UPON |
| COMPLETION OF THE COURSE, FBPE IS TO BE PROVIDED WITH A |
| COPY OF THE COMPLETION CERTIFICATE SO THAT THE |
| ENGINEER?S LICENSE RECORD ON WWW.MYFLORIDALICENSE.COM |
| WEBSITE WILL BE BEEN UPDATED. |
| |
| CURRENTLY, MORE INFORMATION REGARDING THIS COURSE CAN |
| BE FOUND ON THE FBPE HOME PAGE, LATEST NEWS: |
| |
| WWW.FBPE.ORG |
| |
| AND ALSO ON PAGE 4 OF THE FBPE NEWSLETTER: |
| |
| HTTPS://WWW.FBPE.ORG/INDEX.PHP/FILE-DOWNLOADS/SEND/56-2 |
| 015-2016-FBPE-NEWSLETTERS/377-APRIL-2016-FBPE-NEWSLETT |
| ER |
| |
| 9. THREE COMPLETE SETS OF PLANS REQUIRED FOR ALL |
| THRESHOLD (AND RESIDENT INSPECTOR) JOBS, FBC 107. |
| |
| 10. FBC 506, REVISE PLAN TO SHOW THE DISTANCE BETWEEN |
| THE PROPOSED STRUCTURE AND THE EXISTING BLEACHERS, AND |
| PROVIDE DIMENSIONS FOR THE EXISTING BLEACHERS. |
| |
| 11. FBC 506, PROVIDE DIMENSIONS AND IDENTIFICATION FOR |
| THE LARGE UNIDENTIFIED RECTANGLE, NORTHWEST SIDE. |
| |
| 12. FBC 506.2.2, SHOW DISTANCE FROM THE WEST SIDE OF |
| THE BUILDING TO THE FIRE LANE. |
| |
| 13. FBC 107, FS 553.71, SHEET LS101, PROVIDE A TOTAL |
| OCCUPANT LOAD FOR THE BUILDING, BROKEN DOWN BY FLOOR |
| AND OCCUPANCY CLASSIFICATION. |
| |
| 14. LS101, ROOM 145 SHOWS OCCUPANT LOAD CALCULATED AT |
| 100 SF PER PERSON. FBC TABLE 1004.1.2, 50 SF GROSS |
| REQUIRED, PLEASE REVISE. |
| |
| 15. LS101, ROOM 165 APPEARS TO HAVE A TYPO (230 |
| OCCUPANT LOAD). EITHER CORRECT OR PROVIDE ADDITIONAL |
| MEANS OF EGRESS, FBC 1015. |
| |
| 16. LS101, ROOMS 148, 149 152, 159, ANY OTHER ROOMS AS |
| APPLICABLE, PLEASE ROUND UP FOR OCCUPANT LOAD, FBC |
| TABLE 1004.1.2. |
| |
| 17. LS101, SOME ROOMS AND SPACES DO NOT INCLUDE AN |
| OCCUPANT LOAD (137, 138, 139, 140, CORRIDORS, ALL |
| OTHERS AS APPLICABLE). PLEASE REVISE TO INCLUDE, FBC |
| 1004. NOTE THAT DEFINITION (CHAPTER 2) OF FLOOR AREA |
| GROSS INCLUDES ALL AREAS, BUT FLOOR AREA NET EXCLUDES |
| UNOCCUPIED SPACE. ALTHOUGH THIS IS ASSEMBLY OCCUPANCY, |
| TABLE 1004.1.2 UTILIZES GROSS SF FOR THE MAJORITY OF |
| THE SPACES ON THIS FLOOR. PLEASE NOTE THAT THIS |
| RATIONALE IS SUBSTANTIATED BY THE IBC, BUILDING 2012 |
| COMMENTARY. |
| |
| FBC 107, IT IS ACKNOWLEDGED THAT THE ISSUES OF ROUNDING |
| AND MISSING OCCUPANT LOAD WILL LIKELY NOT AFFECT THE |
| LIFE SAFETY DESIGN. HOWEVER, A TOTAL OCCUPANT LOAD IS |
| REQUIRED FOR INFORMATION REQUIRED TO BE ON THE |
| CERTIFICATE OF OCCUPANCY. |
| |
| 18. BREAK ROOM 110 OCCUPANT LOAD APPEARS TO HAVE A TYPO |
| (16 SF RATHER THAN 15 SF), ALSO PLEASE ROUND UP, SEE |
| OTHER COMMENTS, FBC TABLE 1004.1.2. |
| |
| 19. LS101, ACADEMICS TEAM ROOM OCCUPANT LOAD IS SHOWN |
| AS 20 SF PER PERSON, CLARIFY, APPEARS TO BE A TYPO AS |
| THIS SHOULD BE 15 SF (AND OCC LOAD CALCULATED USING 15 |
| SF). REVISE PLAN TO CLARIFY USE OF THE SPACE. 15SF IS |
| FOR AREAS WITH TABLES AND CHAIRS, AREAS WITH CHAIRS |
| ONLY SHOULD USE 7 SF, AND STANDING AREAS SHOULD USE |
| 5SF. |
| |
| 20. LS101, THE ACADEMICS TEAM ROOM MEANS OF EGRESS |
| FORCES THE OCCUPANT TO TRAVEL THROUGH A SPACE WHICH IS |
| A WORK AREA, WHICH APPEARS TO BE PROHIBITED BY FBC |
| 1014.2. REVISE PLAN TO EITHER MODIFY EXITING STRATEGY |
| OR REVISE PLAN TO SHOW COMPLIANCE (I.E., SHOW HOW THE |
| TWO SPACES ARE ACCESSORY TO ONE ANOTHER). |
| |
| IF THE RESUBMITTAL PROPOSES TO MAINTAIN EGRESS FROM AN |
| A2 AREA THROUGH A WORK AREA, PLEASE GET THIS ITEM |
| REVIEWED PRIOR TO RESUBMITTAL VIA EMAIL. |
| |
| 21. LS 101 AND LS 102, NO DIMENSIONS WERE INCLUDED ON |
| THE PLAN, OR ON THE OTHER A SHEETS. ADD OVERALL |
| DIMENSIONS. REVISE PLAN TO SHOW COMMON PATH IN ROOM |
| 145, FBC 1014.3. |
| |
| 22. TRAVEL DISTANCE REQUIREMENTS NOTES ARE INCLUDED IN |
| CODE REVIEW SECTION OF THE LIFE SAFETY PLAN, BUT NO |
| TRAVEL DISTANCES SHOWN. PLEASE REVISE TO INCLUDE WORST |
| CASE, FBC 107. |
| |
| 23. FBC 1022.5 AND .6, MECHANICAL SHEETS APPEAR TO SHOW |
| A DUCT INTO THE EXIT STAIR, PLEASE REMOVE. |
| |
| 24. LS 101, EXITING STRATEGY VESTIBULE 128 IS NOT |
| CLEAR, SEE FBC 1005.7.1, REVISE PLAN TO SHOW COMPLIANCE |
| OR CLARIFY MEANS OF EGRESS PATH. LS101 SHOWS AN ARROW |
| THROUGH THE VESTIBULE, BUT WHEN BOTH DOORS ARE IN THE |
| OPEN POSITION, THE CORRIDOR APPEARS TO BE ALMOST |
| ENTIRELY BLOCKED. |
| |
| 25. FBC 1011.1, REVISE PLAN TO INCLUDE ALL REQUIRED |
| EXIT SIGNS. |
| |
| 26. FBC 107, 1004, 1008, USE OF THE HOSPITALITY SPACES |
| ON THE SECOND FLOOR AND HOW OCCUPANT LOAD WAS |
| DETERMINED IS NOT CLEAR. A TABLE AND CHAIR OCCUPANT |
| LOAD (15SF) WAS USED FOR TERRACES, AND STANDING (5SF) |
| FOR INDOORS. WILL OCCUPANTS NEVER BE ALLOWED TO STAND |
| OUTDOORS IN THE TERRACES? IT IS NOT CLEAR WHY DIFFERENT |
| METHODS WERE USED WHEN IT APPEARS THAT THE TERRACES ARE |
| EXTENSIONS OF THE HOSPITALITY SPACE. IT APPEARS |
| POSSIBLE THAT 5SF PER PERSON SHOULD BE USED FOR THE |
| TERRACES. PROVIDE MORE INFORMATION OR REVISE OCCUPANT |
| LOAD, NUMBER OF EXITS, DOOR SWING. PLEASE CONTACT ME IF |
| YOU WISH TO DISCUSS. |
| |
| 26. FBC 1007, REVISE PLAN TO INDICATE METHOD OF |
| ACCESSIBLE MEANS OF EGRESS SELECTED, REVISE PLAN TO |
| SHOW COMPLIANCE WITH METHOD SELECTED. |
| |
| 27. PROVIDE A DETAIL FOR THE ACCESSIBLE SHOWER, FBC 5TH |
| EDITION ACCESSIBILITY 608. |
| |
| 28. ACCESSIBILITY NOT ADDRESSED ON THIS PLAN: |
| |
| 206.2.13, EXERCISE MACHINES AND EQUIPMENT |
| 241, SAUNAS AND STEAM ROOMS |
| 222, LOCKER ROOMS |
| 226, DINING SURFACES (TERRACES) |
| |
| THESE ITEMS CAN BE ADDRESSED WITH NOTES ON THE PLAN, |
| SHOP DRAWINGS TO BE SUBMITTED PRIOR TO INSTALLATION. |
| |
| 29. AE 112, PROVIDE DIMENSION OF CLEARANCE, 18IN |
| MINIMUM, PULL SIDE, FOR DOOR A121, FBC 5TH ED |
| ACCESSIBILITY FIGURE 404.2.4.1(A). |
| |
| 30. REVISE PLAN TO SHOW COMPLIANCE WITH FBC 404.6, |
| ENCLOSURE OF ATRIUMS (FP SHEETS, LS SHEETS). THE NOTE |
| ON LS SHEETS REFERS TO THE SMOKE PARTITION, BUT I WAS |
| UNABLE TO LOCATE THE REFERENCE TO WINDOW SPRINKLERS. |
| |
| 31. LS101 AND 102, REVISE INTERIOR FINISH NOTES TO |
| INCLUDE ATRIUM REQUIREMENT, FBC 404.8. |
| |
| 32. FBC 107, 703.1, PROVIDE DETAILS (ASSEMBLIES) FOR |
| THE FIRE RATED ELEMENTS. |
| |
| 33. AE801 RATED STUD PARTITION DOES NOT SPECIFY THE UL |
| NUMBER, PLEASE REVISE TO INCLUDE, FBC 703. |
| |
| 34. NOTE CD 01 STATES THIS WAS DESIGNED PER FBC. FBC |
| TABLE 1604.5, RISK CATEGORY III INCLUDES BUILDINGS OF |
| ASSEMBLY OCCUPANCY WITH AN OCCUPANT LOAD OVER 300, |
| SHEET S0.01 INDICATES THIS BUILDING WAS DESIGNED AS |
| RISK CATEGORY II, PLEASE REVISE. |
| |
| 35. PLEASE REVISE FLOOR PLAN TO INCLUDE THE GATE SHOWN |
| ON DETAIL AE712. IF THIS GATE IS IN THE EXIT DISCHARGE, |
| REVISE THE DETAIL TO DEPICT THE REQUIRED PANIC |
| HARDWARE, FBC 1008.2. |
| |
| 36. FBC 1008.1.10, REVISE DOOR SCHEDULE AE701 TO |
| INCLUDE DOOR HARDWARE; IT IS NOT CLEAR WHERE PANIC |
| HARDWARE IS PROPOSED. |
| |
| 37. A SPOT CHECK OF THE ENERGY CALCS WAS DONE; PLEASE |
| CLARIFY THE FOLLOWING OR REVISE PLAN: |
| ROOF INSULATION IS R20 ON ENERGY CALCS, R19 ON PLAN |
| WALL INSULATION IS R3.9 ON ENERGY CALCS, UNABLE TO |
| LOCATE ON PLAN |
| WATER HEATER SECTION IS BLANK |
| EXTERIOR LIGHTING IS BLANK |
| FLOOR R VALUE 3.73, CLARIFY |
| |
| 38. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING |
| PROVISOS: |
| |
| COMPONENTS AND CLADDING PRODUCT APPROVALS REVIEWED BY |
| DESIGNER OF RECORD ARE TO BE SUBMITTED, REVIEWED AND |
| APPROVED PRIOR TO INSTALLATION |
| |
| SEPARATE PERMITS, PLANS, REVIEWS, AND FEES WILL BE |
| REQUIRED FOR SIGNS, AWNINGS, PARKING |
| |
| |
| |
| |