Plan Review Notes
Plan Review Notes For Permit 16050249
Permit Number 16050249
Review Stop B
Sequence Number 1
Notes
Date Text
2016-06-06 11:34:42****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 GOVERNING CODE: FBC 5TH EDITION (FBC 2014)
  
 1. FLORIDA STATUTE 553.71, IT APPEARS THAT THIS
 BUILDING MAY QUALIFY AS A THRESHOLD BUILDING; ANY
 BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DEFINED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SF IN AREA AND AN OCCUPANT CONTENT
 OF GREATER THAN 500 PERSONS.
  
 2. AS A THRESHOLD BUILDING, THE FOLLOWING IS REQUIRED:
  
 A. THRESHOLD INSPECTION PLAN; FS 553.79(5)(A), CITY OF
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 109.3.6.1. THE
 ENFORCING AGENCY SHALL REQUIRE A SPECIAL INSPECTOR TO
 PERFORM STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING
 PURSUANT TO A STRUCTURAL INSPECTION PLAN PREPARED BY
 THE ENGINEER OR ARCHITECT OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO AND APPROVED BY
 THE ENFORCING AGENCY BEFORE THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 B. THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FS
 553.79(5)(A) TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES, NOTARIZED AND RETURNED
 TO THIS OFFICE, REVIEWED AND APPROVED PRIOR TO PERMIT
 ISSUANCE. CONTACT KEN CONRAD, MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM, AT 561-805-6666 FOR ADDITIONAL
 INFORMATION.
 FORMS WERE SENT TO: [email protected]
 ON 5/28/16.
  
 C. SPECIAL INSPECTOR RESUME': PROVIDE A RESUME' OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECTS FOR REVIEW
 BY THE BUILDING OFFICIAL OR HIS DESIGNEE. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
 UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED
 FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA. THE
 RESUME' IS TO BE SUBMITTED TO KEN CONRAD (AND COPY
 SAMANTHA HILL), 561-805-6666, [email protected],
 [email protected]
  
 ALL PROSPECTIVE INSPECTORS ARE TO BE APPROVED BY THE
 CHIEF BUILDING INSPECTOR AND ALL ARE REQUIRED TO SIGN
 THE SPECIAL INSPECTOR AGREEMENT.
  
 D. CONTRACTOR RESUME': PROVIDE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE SUBMITTED TO
 KEN CONRAD, (PLEASE COPY SAMANTHA HILL) VIA E-MAIL
 ([email protected], [email protected]).
  
 E. PERMIT DOCUMENTS: PAPER SUBMITTALS REQUIRE THREE
 SIGNED AND SEALED (IF APPLICABLE) ORIGINAL SETS OF ALL
 DOCUMENTS.
  
 F. THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 MINIMUM BUILDING CODES AND THE APPLICABLE FIRESAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS CHAPTER AND CHAPTER 633.
  
 I WAS UNABLE TO LOCATE THIS STATEMENT ON THE
 ARCHITECT'S PLANS.
  
 THE ENGINEER HAS A SIMILAR STATEMENT BUT LACKS SOME OF
 THE STATUTORY LANGUAGE; PLEASE REVISE.
  
 3. ADVISORY ONLY; PER FS 553.79, ALL SHORING/RE-SHORE
 ENGINEERING IS TO BE REVIEWED BY ENGINEER OF RECORD
 AND THREE SIGNED AND SEALED ORIGINAL SETS ARE TO BE
 SUBMITTED FOR PLAN REVIEW. THE SHORING/RESHORE
 ENGINEERING IS TO BE REVIEWED AND APPROVED PRIOR TO
 INSPECTION. THE CITY APPROVED (CITY STAMPED)
 SHORING/RE-SHORE ENGINEERING IS TO BE AVAILABLE ON THE
 JOB AT THE TIME OF INSPECTION.
  
 4. ADVISORY ONLY; PRIOR TO INSTALLATION, A GUARD RAIL
 DETAIL IS TO BE SUBMITTED FOR PLAN REVIEW. THIS SHOULD
 BE SUBMITTED WITH THE SHORING/RESHORE ENGINEERING.
  
 5. SEE IMPACT FEE REVIEW.
  
 6. ADVISORY ONLY; SEE ROOF (R STOP) REVIEW. NO ROOFING
 INFORMATION PROVIDED IF ROOFING INFORMATION (PRODUCT
 APPROVAL REVIEWED BY DESIGNER OF RECORD, ASSEMBLY
 PROPOSED, ENHANCED FASTENING CALCULATIONS IF REQUIRED)
 IS NOT SUBMITTED PRIOR TO PERMIT ISSUANCE, THIS PERMIT
 WILL BE ISSUED WITH PROVISO. ROOF INFORMATION WILL BE
 REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED PRIOR
 TO INSTALLATION.
  
 7. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. SHEETS C1 THROUGH C4 PREPARED BY RICHARD
 REIKENIS, PE ARE COPIES. THESE PAGES LACK THE
 CERTIFICATE OF AUTHORIZATION, REFERENCE AN OUTDATED
 BUILDING CODE, AND THE SEAL LACKS A DATE. ALSO, PLEASE
 NOTE THAT THIS ENGINEER HAS NOT YET COMPLIED WITH FS
 471.0195, FAC 61G15-22.01 (MANDATORY BY JUNE 30, 2016).
 NOTE THAT THIS ENGINEER, ALTHOUGH RESPONSIBLE FOR CIVIL
 SHEETS, HAS REFERENCED ACCESSIBILITY ON HIS PLAN. SEE
 PAGE 4 OF THE APRIL EDITION OF THE FBPE NEWSLETTER FOR
 MORE INFORMATION:
  
  HTTPS://WWW.FBPE.ORG/INDEX.PHP/FILE-DOWNLOADS/SEND/56-
 2015-2016-FBPE-NEWSLETTERS/377-APRIL-2016-FBPE-NEWSLET
 TER
  
 8. GENERAL ADVISORY TO ALL ENGINEERS WHO DESIGN
 BUILDINGS, STRUCTURES, FACILITIES OR SYSTEMS COVERED BY
 THE FLORIDA BUILDING CODE, ALL ENGINEERS ARE REQUIRED
 TO COMPLETE THE ADVANCED BUILDING CODE COURSE BY JUNE
 30, 2016, FS471.0195 AND FAC61G15-22.001. UPON
 COMPLETION OF THE COURSE, FBPE IS TO BE PROVIDED WITH A
 COPY OF THE COMPLETION CERTIFICATE SO THAT THE
 ENGINEER?S LICENSE RECORD ON WWW.MYFLORIDALICENSE.COM
 WEBSITE WILL BE BEEN UPDATED.
  
 CURRENTLY, MORE INFORMATION REGARDING THIS COURSE CAN
 BE FOUND ON THE FBPE HOME PAGE, LATEST NEWS:
  
 WWW.FBPE.ORG
  
 AND ALSO ON PAGE 4 OF THE FBPE NEWSLETTER:
  
 HTTPS://WWW.FBPE.ORG/INDEX.PHP/FILE-DOWNLOADS/SEND/56-2
 015-2016-FBPE-NEWSLETTERS/377-APRIL-2016-FBPE-NEWSLETT
 ER
  
 9. THREE COMPLETE SETS OF PLANS REQUIRED FOR ALL
 THRESHOLD (AND RESIDENT INSPECTOR) JOBS, FBC 107.
  
 10. FBC 506, REVISE PLAN TO SHOW THE DISTANCE BETWEEN
 THE PROPOSED STRUCTURE AND THE EXISTING BLEACHERS, AND
 PROVIDE DIMENSIONS FOR THE EXISTING BLEACHERS.
  
 11. FBC 506, PROVIDE DIMENSIONS AND IDENTIFICATION FOR
 THE LARGE UNIDENTIFIED RECTANGLE, NORTHWEST SIDE.
  
 12. FBC 506.2.2, SHOW DISTANCE FROM THE WEST SIDE OF
 THE BUILDING TO THE FIRE LANE.
  
 13. FBC 107, FS 553.71, SHEET LS101, PROVIDE A TOTAL
 OCCUPANT LOAD FOR THE BUILDING, BROKEN DOWN BY FLOOR
 AND OCCUPANCY CLASSIFICATION.
  
 14. LS101, ROOM 145 SHOWS OCCUPANT LOAD CALCULATED AT
 100 SF PER PERSON. FBC TABLE 1004.1.2, 50 SF GROSS
 REQUIRED, PLEASE REVISE.
  
 15. LS101, ROOM 165 APPEARS TO HAVE A TYPO (230
 OCCUPANT LOAD). EITHER CORRECT OR PROVIDE ADDITIONAL
 MEANS OF EGRESS, FBC 1015.
  
 16. LS101, ROOMS 148, 149 152, 159, ANY OTHER ROOMS AS
 APPLICABLE, PLEASE ROUND UP FOR OCCUPANT LOAD, FBC
 TABLE 1004.1.2.
  
 17. LS101, SOME ROOMS AND SPACES DO NOT INCLUDE AN
 OCCUPANT LOAD (137, 138, 139, 140, CORRIDORS, ALL
 OTHERS AS APPLICABLE). PLEASE REVISE TO INCLUDE, FBC
 1004. NOTE THAT DEFINITION (CHAPTER 2) OF FLOOR AREA
 GROSS INCLUDES ALL AREAS, BUT FLOOR AREA NET EXCLUDES
 UNOCCUPIED SPACE. ALTHOUGH THIS IS ASSEMBLY OCCUPANCY,
 TABLE 1004.1.2 UTILIZES GROSS SF FOR THE MAJORITY OF
 THE SPACES ON THIS FLOOR. PLEASE NOTE THAT THIS
 RATIONALE IS SUBSTANTIATED BY THE IBC, BUILDING 2012
 COMMENTARY.
  
 FBC 107, IT IS ACKNOWLEDGED THAT THE ISSUES OF ROUNDING
 AND MISSING OCCUPANT LOAD WILL LIKELY NOT AFFECT THE
 LIFE SAFETY DESIGN. HOWEVER, A TOTAL OCCUPANT LOAD IS
 REQUIRED FOR INFORMATION REQUIRED TO BE ON THE
 CERTIFICATE OF OCCUPANCY.
  
 18. BREAK ROOM 110 OCCUPANT LOAD APPEARS TO HAVE A TYPO
 (16 SF RATHER THAN 15 SF), ALSO PLEASE ROUND UP, SEE
 OTHER COMMENTS, FBC TABLE 1004.1.2.
  
 19. LS101, ACADEMICS TEAM ROOM OCCUPANT LOAD IS SHOWN
 AS 20 SF PER PERSON, CLARIFY, APPEARS TO BE A TYPO AS
 THIS SHOULD BE 15 SF (AND OCC LOAD CALCULATED USING 15
 SF). REVISE PLAN TO CLARIFY USE OF THE SPACE. 15SF IS
 FOR AREAS WITH TABLES AND CHAIRS, AREAS WITH CHAIRS
 ONLY SHOULD USE 7 SF, AND STANDING AREAS SHOULD USE
 5SF.
  
 20. LS101, THE ACADEMICS TEAM ROOM MEANS OF EGRESS
 FORCES THE OCCUPANT TO TRAVEL THROUGH A SPACE WHICH IS
 A WORK AREA, WHICH APPEARS TO BE PROHIBITED BY FBC
 1014.2. REVISE PLAN TO EITHER MODIFY EXITING STRATEGY
 OR REVISE PLAN TO SHOW COMPLIANCE (I.E., SHOW HOW THE
 TWO SPACES ARE ACCESSORY TO ONE ANOTHER).
  
 IF THE RESUBMITTAL PROPOSES TO MAINTAIN EGRESS FROM AN
 A2 AREA THROUGH A WORK AREA, PLEASE GET THIS ITEM
 REVIEWED PRIOR TO RESUBMITTAL VIA EMAIL.
  
 21. LS 101 AND LS 102, NO DIMENSIONS WERE INCLUDED ON
 THE PLAN, OR ON THE OTHER A SHEETS. ADD OVERALL
 DIMENSIONS. REVISE PLAN TO SHOW COMMON PATH IN ROOM
 145, FBC 1014.3.
  
 22. TRAVEL DISTANCE REQUIREMENTS NOTES ARE INCLUDED IN
 CODE REVIEW SECTION OF THE LIFE SAFETY PLAN, BUT NO
 TRAVEL DISTANCES SHOWN. PLEASE REVISE TO INCLUDE WORST
 CASE, FBC 107.
  
 23. FBC 1022.5 AND .6, MECHANICAL SHEETS APPEAR TO SHOW
 A DUCT INTO THE EXIT STAIR, PLEASE REMOVE.
  
 24. LS 101, EXITING STRATEGY VESTIBULE 128 IS NOT
 CLEAR, SEE FBC 1005.7.1, REVISE PLAN TO SHOW COMPLIANCE
 OR CLARIFY MEANS OF EGRESS PATH. LS101 SHOWS AN ARROW
 THROUGH THE VESTIBULE, BUT WHEN BOTH DOORS ARE IN THE
 OPEN POSITION, THE CORRIDOR APPEARS TO BE ALMOST
 ENTIRELY BLOCKED.
  
 25. FBC 1011.1, REVISE PLAN TO INCLUDE ALL REQUIRED
 EXIT SIGNS.
  
 26. FBC 107, 1004, 1008, USE OF THE HOSPITALITY SPACES
 ON THE SECOND FLOOR AND HOW OCCUPANT LOAD WAS
 DETERMINED IS NOT CLEAR. A TABLE AND CHAIR OCCUPANT
 LOAD (15SF) WAS USED FOR TERRACES, AND STANDING (5SF)
 FOR INDOORS. WILL OCCUPANTS NEVER BE ALLOWED TO STAND
 OUTDOORS IN THE TERRACES? IT IS NOT CLEAR WHY DIFFERENT
 METHODS WERE USED WHEN IT APPEARS THAT THE TERRACES ARE
 EXTENSIONS OF THE HOSPITALITY SPACE. IT APPEARS
 POSSIBLE THAT 5SF PER PERSON SHOULD BE USED FOR THE
 TERRACES. PROVIDE MORE INFORMATION OR REVISE OCCUPANT
 LOAD, NUMBER OF EXITS, DOOR SWING. PLEASE CONTACT ME IF
 YOU WISH TO DISCUSS.
  
 26. FBC 1007, REVISE PLAN TO INDICATE METHOD OF
 ACCESSIBLE MEANS OF EGRESS SELECTED, REVISE PLAN TO
 SHOW COMPLIANCE WITH METHOD SELECTED.
  
 27. PROVIDE A DETAIL FOR THE ACCESSIBLE SHOWER, FBC 5TH
 EDITION ACCESSIBILITY 608.
  
 28. ACCESSIBILITY NOT ADDRESSED ON THIS PLAN:
  
 206.2.13, EXERCISE MACHINES AND EQUIPMENT
 241, SAUNAS AND STEAM ROOMS
 222, LOCKER ROOMS
 226, DINING SURFACES (TERRACES)
  
 THESE ITEMS CAN BE ADDRESSED WITH NOTES ON THE PLAN,
 SHOP DRAWINGS TO BE SUBMITTED PRIOR TO INSTALLATION.
  
 29. AE 112, PROVIDE DIMENSION OF CLEARANCE, 18IN
 MINIMUM, PULL SIDE, FOR DOOR A121, FBC 5TH ED
 ACCESSIBILITY FIGURE 404.2.4.1(A).
  
 30. REVISE PLAN TO SHOW COMPLIANCE WITH FBC 404.6,
 ENCLOSURE OF ATRIUMS (FP SHEETS, LS SHEETS). THE NOTE
 ON LS SHEETS REFERS TO THE SMOKE PARTITION, BUT I WAS
 UNABLE TO LOCATE THE REFERENCE TO WINDOW SPRINKLERS.
  
 31. LS101 AND 102, REVISE INTERIOR FINISH NOTES TO
 INCLUDE ATRIUM REQUIREMENT, FBC 404.8.
  
 32. FBC 107, 703.1, PROVIDE DETAILS (ASSEMBLIES) FOR
 THE FIRE RATED ELEMENTS.
  
 33. AE801 RATED STUD PARTITION DOES NOT SPECIFY THE UL
 NUMBER, PLEASE REVISE TO INCLUDE, FBC 703.
  
 34. NOTE CD 01 STATES THIS WAS DESIGNED PER FBC. FBC
 TABLE 1604.5, RISK CATEGORY III INCLUDES BUILDINGS OF
 ASSEMBLY OCCUPANCY WITH AN OCCUPANT LOAD OVER 300,
 SHEET S0.01 INDICATES THIS BUILDING WAS DESIGNED AS
 RISK CATEGORY II, PLEASE REVISE.
  
 35. PLEASE REVISE FLOOR PLAN TO INCLUDE THE GATE SHOWN
 ON DETAIL AE712. IF THIS GATE IS IN THE EXIT DISCHARGE,
 REVISE THE DETAIL TO DEPICT THE REQUIRED PANIC
 HARDWARE, FBC 1008.2.
  
 36. FBC 1008.1.10, REVISE DOOR SCHEDULE AE701 TO
 INCLUDE DOOR HARDWARE; IT IS NOT CLEAR WHERE PANIC
 HARDWARE IS PROPOSED.
  
 37. A SPOT CHECK OF THE ENERGY CALCS WAS DONE; PLEASE
 CLARIFY THE FOLLOWING OR REVISE PLAN:
 ROOF INSULATION IS R20 ON ENERGY CALCS, R19 ON PLAN
 WALL INSULATION IS R3.9 ON ENERGY CALCS, UNABLE TO
 LOCATE ON PLAN
 WATER HEATER SECTION IS BLANK
 EXTERIOR LIGHTING IS BLANK
 FLOOR R VALUE 3.73, CLARIFY
  
 38. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING
 PROVISOS:
  
 COMPONENTS AND CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED, REVIEWED AND
 APPROVED PRIOR TO INSTALLATION
  
 SEPARATE PERMITS, PLANS, REVIEWS, AND FEES WILL BE
 REQUIRED FOR SIGNS, AWNINGS, PARKING
  
  
  
  