2016-05-12 03:29:21 | 1) THIS PERMIT APPLICATION IS FOR THE INSTALLATION OF |
| GAS PIPING TO A WATER HEATER, DRYER AND RANGE. THE PLAN |
| THAT WAS SUBMITTED IS SEVERELY LACKING THE PREVIOUSLY |
| REQUESTED INFORMATION. SUBMIT TWO COPIES OF A GAS PLAN |
| THAT CLEARLY REFLECTS THE ENTIRE SCOPE OF WORK TO BE |
| DONE. FBC 107.2.1. 2ND REQUEST. |
| |
| 2) THE FOLLOWING INFORMATION, AT A MINIMUM, SHALL BE |
| SUBMITTED FOR REVIEW: |
| |
| GAS PERMIT APPLICATION REQUIREMENTS |
| |
| 3) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL |
| GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC. |
| G2413. |
| |
| 4.) SHOW THE TYPE (S) OF ALL PIPE MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, AND THE CORRESPONDING EHD |
| NUMBER OF THE CORRUGATED STAINLESS STEEL TUBING |
| (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO |
| FBC SEC.107.2.1. |
| |
| 5) TYPE OF GAS (LP OR NATURAL). |
| |
| 6) BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON |
| THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS SECS.401.8 |
| THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4 (37) OR |
| 2014 FBC-RES. SEC. G2413. |
| |
| 7.) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, |
| (METER OR MP REGULATOR) TO THE MOST REMOTE OUTLET IN |
| THE BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS |
| SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3. |
| |
| 8.) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR ALL |
| APPLIANCES PER THE 2014 FBC-FUEL GAS CODE SEC.304.1 OR |
| 2014 FBC-RES. SEC. G 2407. |
| |
| 9.) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES. |
| SEC. G2413.2. . |
| |
| 10) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE |
| AND TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS |
| SECS. 502 THRU 505 OR 2014 FBC-RES. SEC.G2426. |
| |
| 11). SUBMIT MANUFACTURER'S SPECIFICATION SHEETS / |
| INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014 |
| FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| AND LABELED. |
| |
| 12.) SHOW THE LOCATION OF ALL MEDIUM PRESSURE |
| REGULATORS ( IF APPLICABLE ). A LISTED SHUTOFF VALVE |
| SHALL BE INSTALLED IMMEDIATELY AHEAD OF EACH MP |
| REGULATOR PER 2014 FGC SEC.409.4. |
| |
| 13) SEDIMENT TRAPS SHALL BE INSTALLED IN ACCORDANCE |
| WITH THE 2014 FGC SEC.408.4. |
| |
| 14) SUBMIT TWO COPIES OF THE APPROPRIATE SIZING TABLE |
| FROM THE 2014 FUEL GAS CODE FOR THE SIZING OF THIS |
| SYSTEM. FBC 107.2.1. |
| |
| NOTE: IT IS OBVIOUS THAT MY REVIEW COMMENTS HAVE NOT |
| BEEN ADDRESSED OR EVEN READ. IF THE GAS PLAN GETS |
| TURNED DOWN AGAIN, 4 TIMES THE PLAN REVIEW FEE SHALL BE |
| PAID AT THE TIME OF RESUBMITTAL IN ACCORDANCE WITH FLA. |
| STATUTE 553.80 (2) ( B). |
| |