Plan Review Notes For Permit 16050165 |
Permit Number |
16050165 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-05-11 16:46:56 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #16050165 | | 5/11/16 | | | | 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW | | 3-TON RTU- SECTION C403.2.1 FBC-14 ENERGY CONSERVATION. | | 2) PROVIDE EXHAUST VENTILATION FOR THE KITCHENETTE- | | TABLE 6-4 ASHRAE 62.1-2010. | | 3) PROVIDE A MECHANICAL ROOF PLAN SHOWING LOCATION OF | | THE NEW RTU AND THE CONDENSATE PIPE DISPOSAL RUN AND | | DISCHARGE LOCATION. | | 4) PROVIDE SHUTOFF DAMPER CONTROLS FOR THE O/A- SECTION | | C403.2.4.4 FBC-14 ENERGY. | | 5) THE RTU ANCHORING DETAIL IS INCOMPLETE: A) PROVIDE | | COMPLETE WIND LOAD DESIGN CRITERIA- INCLUDING THE | | EXPOSURE CATEGORY AND HEIGHT ADJUSTMENT COEFFICIENT, | | AND DESIGN PRESSURES. B) INDICATE HOW THE CURB WILL BE | | ATTACHED TO THE ROOF STRUCTURE | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|