Plan Review Notes For Permit 16050165 |
Permit Number |
16050165 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-05-10 13:51:10 | INITIAL ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 NEC | | COMMENTS: | | | | 1. PLEASE CLARIFY OR CORRECT CIRCUIT #8 SHOWN AS A | | 2POLE 60 AMP BREAKER ON A #12 CONDUCTOR. FBC 107.3.5 | | 2. SHOW THAT THERE IS A WP/GFCI RECEPTACLE WITHIN 25FT | | OF THE ROOFTOP UNITS ON THE FLOOR PLAN. NEC 210.63 | | 3. PROVIDE A NOTE TO INDICATE REQUIRED LOW VOLTAGE | | SYSTEMS (ACCESS, DATA ETC.) SEPARATE PERMITS. A NOTE | | WILL SUFFICE. | | 4. PLEASE LABEL GFCI PROTECTED ALL RECEPTACLES IN THE | | BREAK ROOM WITHIN 6FT OF SINK. NEC 210.8B7 | | 5. PROVIDE A NOTE TO INDICATE REQUIREMENTS OF NEC | | 410.130G1-REQUIRED DISCONNECTING MEAN FOR ALL | | FLORESCENT LUMINAIRES THAT UTILIZE DOUBLE ENDED LAMPS, | | SEE VERBIAGE IN CODE. | | 6. PROVIDE SIZE OF THE EXISTING 3RD FLA WEST MAIN | | BREAKER. | | 7. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY | | QUESTIONS REGARDING THIS PROJECT. | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | |
|