2016-05-10 13:51:10INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE CLARIFY OR CORRECT CIRCUIT #8 SHOWN AS A
 2POLE 60 AMP BREAKER ON A #12 CONDUCTOR. FBC 107.3.5
 2. SHOW THAT THERE IS A WP/GFCI RECEPTACLE WITHIN 25FT
 OF THE ROOFTOP UNITS ON THE FLOOR PLAN. NEC 210.63
 3. PROVIDE A NOTE TO INDICATE REQUIRED LOW VOLTAGE
 SYSTEMS (ACCESS, DATA ETC.) SEPARATE PERMITS. A NOTE
 WILL SUFFICE.
 4. PLEASE LABEL GFCI PROTECTED ALL RECEPTACLES IN THE
 BREAK ROOM WITHIN 6FT OF SINK. NEC 210.8B7
 5. PROVIDE A NOTE TO INDICATE REQUIREMENTS OF NEC
 410.130G1-REQUIRED DISCONNECTING MEAN FOR ALL
 FLORESCENT LUMINAIRES THAT UTILIZE DOUBLE ENDED LAMPS,
 SEE VERBIAGE IN CODE.
 6. PROVIDE SIZE OF THE EXISTING 3RD FLA WEST MAIN
 BREAKER.
 7. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  