2016-05-25 15:32:331501 NORTHPOINT PARKWAY SUITE #104
 PERMIT #16050132
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLANS ARE NOT TO SCALE.
  
 SEVERAL ROOMS DO NOT INDICATE A NAME/FUNTION.
  
 NO CEILING HEIGHTS INDICATED FOR CEILING MOUNTED
 APPLIANCES.
  
 NOTE #23 INDICATES THIS IS A STORAGE OCCUPANCY;
 HOWEVER, MORE THAN HALF OF THE SUITE IS BUSINESS
 OCCUPANCY WITH AN ASSUMED AMBIENT NOISE OF 55DB.
 PROVIDING AN ASSUMED SOUND LEVEL OF 58DB WILL NOT BE
 SUFFICIENT.
  
 INSUFFICIENT NOTIFICATION DEVICES IN SEVERAL OFFICE
 AREAS.
  
 PLANS DO NOT SHOW ANY DUCT SMOKE DETECTORS. CONFIRM
 HVAC UNITS ARE NOT SUPPLYING MORE THAN 2,000 CFM.
  