Plan Review Notes For Permit 16050123 |
Permit Number |
16050123 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-05-05 11:17:55 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 516-805-6713 | | [email protected] | | | | - PROVIDE LOAD CALCULATIONS , A PANEL SCHEDULE SHOWING | | ACTUAL CIRCUITS / CONDUCTORS / BREAKER SIZES. NEC 215.5 | | WPBA 107 | | | | - GROUNDING DETAIL TO INCLUDE INTERSYSTEM BONDING | | TERMINAL STRIP | | | | - NOTICE TO ELECTRICAL CONTRACTOR SMOKE ALARMS REQUIRED | | PER RESIDENTIAL CODE SECTIONS 314 & 315. |
|