Plan Review Notes For Permit 16050027 |
Permit Number |
16050027 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-05-13 12:00:59 | INITIAL ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA RES BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 | | COMMENTS: | | | | 1. A PANEL BOARD MUST BE AT THE NEW DETACHED STRUCTURE | | AND A GROUNDING ELECTRODE CONDUCTOR MUST BE SHOWN PER | | E3607.3. SHOW PANEL LOCATION ON FLOOR PLAN OF DETACHED. | | 2. PLEASE SHOW THE FEEDER CONDUCTOR SIZES AND EQUIPMENT | | GROUNDING CONDUCTOR REQUIRED WITH THESE FEEDERS. FBC | | 107.3.5 | | 3. SHOW ONE LINE REFLECTING SERVICE AND DETACHED BEING | | FED PER COMMENT ABOVE. FBC 107.3.5 | | 4. PROVIDE GENERAL NOTES TO INDICATE REQUIREMENTS FOR | | AFCI PROTECTION, TAMPER RESISTANT RECEPTACLES. FBC RES | | E3902 E4002.14 | | 5. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY | | QUESTIONS OR CONCERNS. | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | |
|