2016-05-13 12:00:59INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. A PANEL BOARD MUST BE AT THE NEW DETACHED STRUCTURE
 AND A GROUNDING ELECTRODE CONDUCTOR MUST BE SHOWN PER
 E3607.3. SHOW PANEL LOCATION ON FLOOR PLAN OF DETACHED.
 2. PLEASE SHOW THE FEEDER CONDUCTOR SIZES AND EQUIPMENT
 GROUNDING CONDUCTOR REQUIRED WITH THESE FEEDERS. FBC
 107.3.5
 3. SHOW ONE LINE REFLECTING SERVICE AND DETACHED BEING
 FED PER COMMENT ABOVE. FBC 107.3.5
 4. PROVIDE GENERAL NOTES TO INDICATE REQUIREMENTS FOR
 AFCI PROTECTION, TAMPER RESISTANT RECEPTACLES. FBC RES
 E3902 E4002.14
 5. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  