2016-06-29 09:30:23 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) PROVIDE A COMPLETE DESCRIPTION OF WORK ON THE PLANS. |
| INDICATE WHICH WINDOWS AND DOORS ARE TO BE REPLACED. |
| FBC 107.2.1 |
| |
| 2) THIS APPEARS TO BE A LEVEL 3 ALTERATION. PROVIDE A |
| FLOOR PLAN OF THE EXISTING BUILDING. FBC EXISTING |
| BUILDING 505 AND FBC 107.2.1 |
| |
| 3) SHOW COMPLIANCE WITH FBC ENERGY CONSERVATION SECTION |
| R101.4.3 BY SUBMITTING THE REQUIRED CONSTRUCTION |
| DOCUMENTS. FBC ENERGY CONSERVATION R101.5.1 |
| |
| 4) PROVIDE ADDITIONAL DETAILS ON THE STEEL COLUMN CAP |
| INCLUDING THE WELDS. FBC 107.2.1 |
| |
| 5) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 |
| THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT |
| APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION |
| INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF |
| THE DIFFERENT ROOFING MATERIALS, WINDOW/GLASS TYPES, |
| IMPACT PROTECTION DEVICES AND EXTERIOR DOOR TYPES. |
| |
| 6) ON SHEETS 3 AND 8, THE CONSTRUCTION TYPE SHOULD BE |
| V-B AND THE OCCUPANCY IS R-3 SINGLE FAMILY DWELLING. ON |
| SHEET 3 THE 2010 FBC EDITION OF THE CODE IS CITED AND |
| IT SHOULD BE THE 2014 FBC. |
| |
| 7) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A |
| RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| COMMENTS HAS BEEN ADDRESSED. |
| |
| |
| |