2016-06-29 09:30:23PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE A COMPLETE DESCRIPTION OF WORK ON THE PLANS.
 INDICATE WHICH WINDOWS AND DOORS ARE TO BE REPLACED.
 FBC 107.2.1
  
 2) THIS APPEARS TO BE A LEVEL 3 ALTERATION. PROVIDE A
 FLOOR PLAN OF THE EXISTING BUILDING. FBC EXISTING
 BUILDING 505 AND FBC 107.2.1
  
 3) SHOW COMPLIANCE WITH FBC ENERGY CONSERVATION SECTION
 R101.4.3 BY SUBMITTING THE REQUIRED CONSTRUCTION
 DOCUMENTS. FBC ENERGY CONSERVATION R101.5.1
  
 4) PROVIDE ADDITIONAL DETAILS ON THE STEEL COLUMN CAP
 INCLUDING THE WELDS. FBC 107.2.1
  
 5) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF
 THE DIFFERENT ROOFING MATERIALS, WINDOW/GLASS TYPES,
 IMPACT PROTECTION DEVICES AND EXTERIOR DOOR TYPES.
  
 6) ON SHEETS 3 AND 8, THE CONSTRUCTION TYPE SHOULD BE
 V-B AND THE OCCUPANCY IS R-3 SINGLE FAMILY DWELLING. ON
 SHEET 3 THE 2010 FBC EDITION OF THE CODE IS CITED AND
 IT SHOULD BE THE 2014 FBC.
  
 7) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  