2016-05-09 12:50:451ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16050024
 5/9/16
  
 1) THE SUBMITTED PLANS FOR THE NEW SURGICAL CENTER DO
 NOT REFLECT APPLICABLE AND COMPLIANT CODE DESIGN, AND
 MUST BE REVISED TO PROVIDE ENOUGH INFORMATION FOR A
 COMPLETE MECHANICAL REVIEW.
 A) REFER TO SECTION 451 AMBULATORY SURGICAL CENTERS
 FBC-14 BUILDING AND PROVIDE DOCUMENTATION OF PLAN
 APPROVAL FROM AHCA- SECTION 451.1.5.
 B) IN ADDITION TO THE LIST OF APPLICABLE CODES ON SHEET
 CVR, THE PLANS SHALL ALSO BE DESIGNED IN ACCORDANCE
 WITH- SECTION 451.2.1: THE FIRE CODES DESCRIBED IN
 CHAPTER 69A-3.012, STANDARDS OF THE NATIONAL FIRE
 PROTECTION ASSOCIATION ADOPTED, FLORIDA ADMINISTRATIVE
 CODE & SECTION AND 451.2.2: GUIDELINES FOR DESIGN AND
 CONSTRUCTION OF HEALTH CARE FACILITIES AND ASHRAE
 170-2008.
 2) THE PLANS APPEAR TO INDICATE AN "OUTPATIENT"
 SURGICAL FACILITY. PLEASE REFER TO SECTION 3.1-8.2.1.1
 GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH CARE
 FACILTIES. REVIEW ALL SUB-SECTIONS AND ASHRAE 170-2008
 (PART 6 OF THE GUIDELINES) AND RE-DESIGN THE HVAC
 SYSTEMS ACCORDINGLY. PLEASE SEE TABLE 7-1 DESIGN
 PARAMETERS ASHRAE 170 FOR VENTILATION REQUIREMENTS.
 PROVIDE A VENTILATION TABLE ON THE PLAN FOR ALL ROOMS
 AND SPACES IN ACCORDANCRE WITH THE TABLE.
 3) THE CURRENT PLAN SHOWS A TRANSFER GRILL AT THE
 JANITOR/CORRIDOR, HOWEVER CORRIDORS SHALL NOT SERVE AS
 RETURN AIR DUCTS- SECTION 601.2 FBC-14 MECHANICAL.
 PLEASE CORRECT THE PLAN
 4) PLEASE INDICATE WHICH THE FRICTION RATE USED TO SIZE
 THE NEW SUPPLY AND RETURN DUCTS- THE MAIN DUCT TRUNKS
 APPEAR UNDERSIZED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  