2016-05-09 12:50:45 | 1ST REVIEW: FBC 2014 MECHANICAL |
| PERMIT #16050024 |
| 5/9/16 |
| |
| 1) THE SUBMITTED PLANS FOR THE NEW SURGICAL CENTER DO |
| NOT REFLECT APPLICABLE AND COMPLIANT CODE DESIGN, AND |
| MUST BE REVISED TO PROVIDE ENOUGH INFORMATION FOR A |
| COMPLETE MECHANICAL REVIEW. |
| A) REFER TO SECTION 451 AMBULATORY SURGICAL CENTERS |
| FBC-14 BUILDING AND PROVIDE DOCUMENTATION OF PLAN |
| APPROVAL FROM AHCA- SECTION 451.1.5. |
| B) IN ADDITION TO THE LIST OF APPLICABLE CODES ON SHEET |
| CVR, THE PLANS SHALL ALSO BE DESIGNED IN ACCORDANCE |
| WITH- SECTION 451.2.1: THE FIRE CODES DESCRIBED IN |
| CHAPTER 69A-3.012, STANDARDS OF THE NATIONAL FIRE |
| PROTECTION ASSOCIATION ADOPTED, FLORIDA ADMINISTRATIVE |
| CODE & SECTION AND 451.2.2: GUIDELINES FOR DESIGN AND |
| CONSTRUCTION OF HEALTH CARE FACILITIES AND ASHRAE |
| 170-2008. |
| 2) THE PLANS APPEAR TO INDICATE AN "OUTPATIENT" |
| SURGICAL FACILITY. PLEASE REFER TO SECTION 3.1-8.2.1.1 |
| GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH CARE |
| FACILTIES. REVIEW ALL SUB-SECTIONS AND ASHRAE 170-2008 |
| (PART 6 OF THE GUIDELINES) AND RE-DESIGN THE HVAC |
| SYSTEMS ACCORDINGLY. PLEASE SEE TABLE 7-1 DESIGN |
| PARAMETERS ASHRAE 170 FOR VENTILATION REQUIREMENTS. |
| PROVIDE A VENTILATION TABLE ON THE PLAN FOR ALL ROOMS |
| AND SPACES IN ACCORDANCRE WITH THE TABLE. |
| 3) THE CURRENT PLAN SHOWS A TRANSFER GRILL AT THE |
| JANITOR/CORRIDOR, HOWEVER CORRIDORS SHALL NOT SERVE AS |
| RETURN AIR DUCTS- SECTION 601.2 FBC-14 MECHANICAL. |
| PLEASE CORRECT THE PLAN |
| 4) PLEASE INDICATE WHICH THE FRICTION RATE USED TO SIZE |
| THE NEW SUPPLY AND RETURN DUCTS- THE MAIN DUCT TRUNKS |
| APPEAR UNDERSIZED. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |