2016-05-04 16:16:19 | 1ST ELECTRICAL REVIEW NOTES |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| |
| CORRECTIONS REQUIRED: |
| 1. NEC 422.31(B), A DISCONNECT IS MISSING FOR THE |
| ELECTRIC WATER HEATER. |
| 2. LABEL FOR PANEL N ON THE SCHEDULE INDICATES EXISTING |
| WHILE THE RISER SAYS IT IS NEW. CORRECT TO MATCH AND |
| CLARIFY. |
| 3. NEC 110.16 ALL ELECTRICAL EQUIPMENT SHALL BE MARKED |
| WITH THE ARC-FLASH HAZARD WARNING LABELS. |
| 4. NEC110.24 ALL ELECTRICAL APPARATUS SHALL BE DURABLY |
| DATE MARKED WITH THE MAXIMUM AVAILABLE FAULT CURRENT. |
| 5. NEC 215.5 ALONG WITH THE RISER DIAGRAM YOU NEED TO |
| SUBMIT LOAD CALCS FOR THE ADDED LOAD. |
| 6. FBC-EC405 MANDATORY LIGHTING CONTROLS ARE REQUIRED. |
| LIGHTING CONTROL MISSING FOR ROOMS 1007, 108 & 109. |
| 7. FBC-EC405.5.2 PROVIDE A LIGHT DENSITY ALLOWANCE |
| CHART SHOWING ENERGY CODE COMPLIANCE. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |
| PH: 561-805-6746 |
| EMAIL: [email protected] |
| |