Plan Review Notes
Plan Review Notes For Permit 16050022
Permit Number 16050022
Review Stop B
Sequence Number 3
Notes
Date Text
2017-04-26 11:49:41PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. THE PRODUCT APPROVALS ARE REQUIRED TO BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD.
  
 2) ON THE ENERGY FORM R405-2014, THE NUMBERS FOR THE
 COOLING BTUS AND THE SEER ARE SWITCHED. THE SEER SHOULD
 BE 16 AND THE BTUS SHOULD BE 18,000. FBC 107.2.1
  
 3) THE AHRI CERTIFICATION LETTER DOES NOT MATCH THE
 MODELS SPECIFIED ON THE PLANS. FBC 107.2.1