2016-09-06 18:58:28PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF ENERGY CODE COMPLIANCE FORMS THAT
 HAVE THE SIGNATURES OF THE PREPARER AND THE
 OWNER/AGENT. FBC ENERGY CONSERVATION R103 - COMPLETED
 FORMS R402 OR R405 ARE ACCEPTABLE.
  
 2) PROVIDE SIGNED AND SEALED CALCULATIONS TO VERIFY
 THAT THE (2) 2 X 12 BEAM SPANNING 15 FEET CAN SUPPORT
 THE 40 PSF LIVE LOAD AND DEAD LOAD OF THE BALCONY. FBC
 107.2.1.3
  
 3) THE PLANS DO NOT SPECIFY ANY CROSS BRACING OF THE
 DECK OR THE 4 X 4 POSTS THAT ARE SUPPORTING THE DECK.
 PROVIDE SIGNED AND SEALED CALCULATIONS TO SHOW THAT THE
 4" X 4" X 8' WOOD POSTS ARE CAPABLE OF RESISTING THE
 LATERAL LOADS, WIND LOADS, ETC.
  
 4) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR THE RIDGE
 OR ROOF VENT, THE SIDING (IF IT IS ALUMINUM OR VINYL)
 AND THE ALUMINUM SOFFIT MATERIAL.
  
 5) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE
 SINGLE OUTSWING DOOR HAS A MAXIMUM NEGATIVE DESIGN
 PRESSURE FOR THE DOOR OF (-50 PSF) IS NOT ADEQUATE FOR
 THE DOOR LOCATED ON THE FIRST FLOOR IN THE END ZONE,
 WHICH REQUIRES -54.8 PSF. SUBMIT CORRECT PRODUCT
 APPROVALS. FBC-R301.2.1
  
 6) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE
 SECTIONAL GARAGE DOOR HAS MAXIMUM DESIGN PRESSURES OF
 +36, -42.5 PSF WHICH ARE NOT ADEQUATE. THE PLANS
 SPECIFY THAT THE REQUIRED PRESSURES ARE +37.5, -42.5
 PSF. SUBMIT CORRECT PRODUCT APPROVALS. FBC-R301.2.1
  
 7) SUBMIT TWO COPIES OF THE PRODUCT EVALUATION REPORTS
 WITH INSTALLATION REQUIREMENTS FOR THE OPEN CELL SPRAY
 FOAM INSULATION THAT IS SPECIFIED ON THE PLANS. FBC
 R316
  
 8) THE SECOND FLOOR OF THIS STRUCTURE IS CONDITIONED
 SPACE. THE FLOOR/CEILING ASSEMBLY ABOVE THE GARAGE IS
 REQUIRED TO HAVE THERMAL INSULATION. FBC ENERGY
 CONSERVATION R402.1
  
 9) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  