Plan Review Notes
Plan Review Notes For Permit 16050022
Permit Number 16050022
Review Stop E
Sequence Number 1
Notes
Date Text
2016-05-13 11:55:56INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. SHOW A SMOKE DETECTOR AT THE LANDING AREA OF STAIRS
 AND THROUGHOUT PER FBC RES 314 & 315.
 2. GENERAL NOTE TO INDICATED REQUIRED SEPARATE PERMITS
 FOR LOW VOLTAGE SYSTEMS.
 3. PANEL BOARD MUST BE AT THE NEW DETACHED STRUCTURE
 AND A GROUNDING ELECTRODE CONDUCTOR MUST BE SHOWN PER
 E3607.3. SHOW PANEL LOCATION ON FLOOR PLAN OF DETACHED.
 4. PLEASE SHOW THE FEEDER CONDUCTOR SIZES AND EQUIPMENT
 GROUNDING CONDUCTOR REQUIRED WITH THESE FEEDERS. FBC
 107.3.5
 5. PROVIDE PANEL SCHEDULE ON SHEET 6 OF THIS STRUCTURE.
 FBC 107.3.5
 6. PROVIDE GENERAL NOTES TO INDICATE REQUIREMENTS FOR
 AFCI PROTECTION, TAMPER RESISTANT RECEPTACLES. FBC RES
 E3902 E4002.14
 7. GARAGE DOOR OPENER TO BE LABELED GFCI PROTECTED PER
 FBC RES E3902.2
 8. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  