2016-05-13 11:55:56 | INITIAL ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA RES BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 | | COMMENTS: | | | | 1. SHOW A SMOKE DETECTOR AT THE LANDING AREA OF STAIRS | | AND THROUGHOUT PER FBC RES 314 & 315. | | 2. GENERAL NOTE TO INDICATED REQUIRED SEPARATE PERMITS | | FOR LOW VOLTAGE SYSTEMS. | | 3. PANEL BOARD MUST BE AT THE NEW DETACHED STRUCTURE | | AND A GROUNDING ELECTRODE CONDUCTOR MUST BE SHOWN PER | | E3607.3. SHOW PANEL LOCATION ON FLOOR PLAN OF DETACHED. | | 4. PLEASE SHOW THE FEEDER CONDUCTOR SIZES AND EQUIPMENT | | GROUNDING CONDUCTOR REQUIRED WITH THESE FEEDERS. FBC | | 107.3.5 | | 5. PROVIDE PANEL SCHEDULE ON SHEET 6 OF THIS STRUCTURE. | | FBC 107.3.5 | | 6. PROVIDE GENERAL NOTES TO INDICATE REQUIREMENTS FOR | | AFCI PROTECTION, TAMPER RESISTANT RECEPTACLES. FBC RES | | E3902 E4002.14 | | 7. GARAGE DOOR OPENER TO BE LABELED GFCI PROTECTED PER | | FBC RES E3902.2 | | 8. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY | | QUESTIONS OR CONCERNS. | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | |
|