Plan Review Notes For Permit 16050012 |
Permit Number |
16050012 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-05-04 06:32:08 | 1) THERE ARE OTHER GAS APPLIANCES CONNECTED TO THIS GAS | | SYSTEM (SEE PLAN IN POOL HEATER APPLICATION FOLDER). | | THE CONSUMER LINE FROM THE METER WILL BE UNDER SIZED AT | | 1 1/4 INCHES AS PRESENTLY SHOWN. THE CONSUMER LINE | | SHALL BE INCREASED TO 1 1/2 INCHES PER TABLE 402.4 (2) | | OF 2014 FGC. SHOW THIS ON YOUR DRAWING AND LIST THE | | EXISTING APPLIANCES AND THEIR BTU LOAD ON THE PLANS AND | | ALSO THE ENTIRE BBTU LOAD ON THE SYSTEM AND THE PSI OF | | THE SYSTEM.2014 FGC SEC.402.2. | | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POOL | | HEATER.FBC 107.2.1. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|