Plan Review Notes For Permit 16041291 |
Permit Number |
16041291 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-05-02 14:06:25 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 516-805-6713 | | [email protected] | | | | | | - PROVIDE GROUNDING DETAIL SHOWING GROUNDING ELECTRODE | | SYSTEM IN ACCORDANCE WITH NEC 250.50 AND 250.94 | | INTERSYSTEM BONDING. | | SHOW EXISTING RISER WIRE SIZE AND PROVIDE LOAD CALCS TO | | VERIFY LOAD DEMANDS, A MORE ACCURATE PANEL SCHEDULE | | SHOWING EXISTING CIRCUITS. WPBA 107 | | | | - NEC 225.37 IDENTIFICATION. WHERE A BUILDING OR | | STRUCTURE HAS ANY | | COMBINATION OF FEEDERS, BRANCH CIRCUITS, OR SERVICES | | PASSING | | THROUGH IT OR SUPPLYING IT, A PERMANENT PLAQUE OR | | DIRECTORY | | SHALL BE INSTALLED AT EACH FEEDER AND BRANCH-CIRCUIT | | DISCONNECT | | LOCATION DENOTING ALL OTHER SERVICES, FEEDERS, OR | | BRANCH CIRCUITS | | SUPPLYING THAT BUILDING OR STRUCTURE OR PASSING THROUGH | | THAT | | BUILDING OR STRUCTURE AND THE AREA SERVED BY EACH. | | | | - NEC 408.4(B) PANEL BOARDS SHALL HAVE A LABEL MARKING | | WERE THE LOCATION OF THE SOURCE OF POWER SUPPLY. |
|