Plan Review Notes For Permit 16041215 |
Permit Number |
16041215 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-05-25 17:26:43 | | | PLUMBING PROVISO | | 4 OF THE 9 DRINKING FOUNTAINS SHALL COMPLY WITH FBC | | ACC. SEC. 602.7 DRINKING FOUNTAINS FOR STANDING | | PERSONS. | | SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING | | PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43 | | INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR | | GROUND. | | TO MEET THE REQUIREMENTS OF FBC ACC. SEC. | | 211.3 MORE THAN MINIMUM NUMBER. | | WHERE MORE THAN THE MINIMUM NUMBER OF DRINKING | | FOUNTAINS SPECIFIED IN 211.2 ARE PROVIDED, 50 PERCENT | | OF THE TOTAL NUMBER OF DRINKING FOUNTAINS PROVIDED | | SHALL COMPLY WITH 602.1 THROUGH 602.6, AND 50 PERCENT | | OF THE TOTAL NUMBER OF DRINKING FOUNTAINS PROVIDED | | SHALL COMPLY WITH 602.7. | | | | | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|