Plan Review Notes
Plan Review Notes For Permit 16041215
Permit Number 16041215
Review Stop ENG
Sequence Number 2
Notes
Date Text
2016-06-01 08:50:51PROVISOS:
  
 1. CIVIL PLANS ARE UNDER REVIEW THRU ENGINEERING
 SERVICES, A SEPARATE PERMIT IS REQUIRED FOR FIRELINE
 ON-SITE.
 THIS SHALL INCLUDE SUBMISSION OF CIVIL PLANS SHEET C-1
 THRU C-9 TO OBTAIN A UG FIRELINE, FA OR FS PERMIT.
 INCLUDE ON PLANS THE FIRE HYDRANT PRESSURE TEST, TIME,
 LOCATION, WHO PERFORMED THE TEST AND RESULTS.
  
 2. CIVIL PLANS REQUIRE PALM BEACH COUNTY HEALTH
 DEPARTMENT REVIEW AND APPROVAL.
  
 3. A RIGHT-OF-WAY PERMIT THRU ENGINEERING WILL ALSO BE
 REQUIRED FOR CITY UTILITY WORK.
  
 4. CONTRACTOR SHALL USE THE CITY'S ENGINEERING STANDARD
 DETAILS AVAILABLE.
 HTTP://WPBFL.US/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FO
 RMS,-PERMITS-APPLICATIONS
 INCLUDING "PRESSURE PIPE" SERIES.
  
 5. A PRE-CONSTRUCTION MEETING WILL BE REQUIRED WITH THE
 CITY OF WPB ENGIEERING DEPARTMENT PRIOR TO ANY PUBLIC
 UTILITY EXCAVATIONS.
  
 6. SEC. 90-203. - PROHIBITED DISCHARGES; ILLICIT
 CONNECTIONS.
 (A) GENERAL PROHIBITION. EXCEPT AS PROVIDED IN SECTION
 90-205, AND EXCEPT PURSUANT TO A VALID NPDES PERMIT, IT
 SHALL BE UNLAWFUL FOR ANY PERSON TO DIRECTLY OR
 INDIRECTLY DEPOSIT, DISCHARGE, SPILL, OR DUMP INTO ANY
 OF THE PUBLIC WATERS OR MUNICIPAL SEPARATE STORM SEWER
 SYSTEM WITHIN THE CITY, ANY SUBSTANCE OTHER THAN THAT
 COMPOSED ENTIRELY OF STORMWATER.
 (B) SITE OF INDUSTRIAL ACTIVITY. EXCEPT AS PROVIDED IN
 SECTION 90-205, ANY DIRECT OR INDIRECT DISCHARGE FROM A
 SITE OF INDUSTRIAL ACTIVITY TO THE SEPARATE STORM SEWER
 SYSTEM OWNED BY THE CITY WHICH DOES NOT COMPLY WITH, OR
 IS NOT PURSUANT TO, A VALID NPDES PERMIT IS PROHIBITED.
 (C) ILLICIT CONNECTIONS. NO PERSON MAY MAINTAIN, USE OR
 ESTABLISH ANY DIRECT OR INDIRECT CONNECTION TO THE
 STORMWATER SYSTEM THAT RESULTS IN ANY DISCHARGE IN
 VIOLATION OF THIS ARTICLE. THIS PROHIBITION IS
 RETROACTIVE AND APPLIES TO CONNECTIONS MADE IN THE
 PAST, REGARDLESS OF WHETHER MADE UNDER A PERMIT, OR
 OTHER AUTHORIZATION, OR WHETHER PERMISSIBLE UNDER LAWS
 OR PRACTICES APPLICABLE OR PREVAILING AT THE TIME THE
 CONNECTION WAS MADE. (CODE 1979, 32-18)
  
 7. NOTIFY - PERVIOUS AND IMPERVIOUS AREAS CALCULATIONS
 TO CITY OF WEST PALM BEACH ENGINEERING DEPARTMENT.
  
 8. ANY SIDEWALKS OR ADA PATHS NEAR AND ALONG THE
 PERIMETER OF THE PROPERTY SHALL CONFORM TO ADAAG
 STANDARDS FOR MINIMUM SLOPE AND WIDTH ACCESS.
  
 9. ANY EXISTING PUBLIC UTILITY CONNECTION NOT NEEDED
 FOR USE OF THE DEVELOPMENT SHALL BE CUT AND CAPPED AT
 THE MAIN. ANY DEVIATION OR HARDSHIP MAY BE EXPRESSED IN
 WRITING TO THE CITY OF WEST PALM BEACH PUBLIC UTILITY
 DIRECTOR IN WRITING. PLAN SHOWS WATER AND SEWER
 SERVICES THAT WILL NOT BE USED.
  
 10. CALL 811 BEFORE DIG, SHALL BE IN ALL UTILITY PLANS.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  
  
  
  