2016-05-02 16:24:351ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16041215
 5/2/16
  
 1) THE IAQ PROCEDURE FOR OUTDOOR AIR INTAKE REQUIRES
 SUBMITTAL OF DESIGN DOCUMENTATION AS INDICATED IN
 SECTION 6.3.6 ASHRAE 62.1-2010:
 6.3.6 DOCUMENTATION. WHEN THE IAQ PROCEDURE IS USED,
 THE FOLLOWING INFORMATION SHALL BE INCLUDED IN THE
 DESIGN DOCUMENTATION: THE CONTAMINANTS OF CONCERN
 CONSIDERED IN THE DESIGN PROCESS, THE SOURCES AND
 EMISSION RATES OF THE CONTAMINANTS OF CONCERN, THE
 CONCENTRATION LIMITS AND EXPOSURE PERIODS AND THE
 REFERENCES FOR THESE LIMITS, AND THE ANALYTICAL
 APPROACH USED TO DETERMINE VENTILATION RATES AND AIR
 CLEANING REQUIREMENTS. THE CONTAMINANT MONITORING AND
 OCCUPANT AND/OR VISITOR EVALUATION PLANS SHALL ALSO BE
 INCLUDED IN THE DOCUMENTATION.
 PLEASE REVIEW ALL SUB-SECTIONS LISTED UNDER 6.3 AND
 SHOW COMPLIANCE.
  
 2) SHEET M-001: PLEASE UPDATE THE ASHRAE 62.1-2007
 REFERENCE SHOWN IN THE O/A TABLE TO THE CURRENT 2010
 EDITION.
  
 3) M-001: IT APPEARS THAT THE SYSTEM DATA IN THE AC
 SCHEDULE FOR AHU-11 IS LISTED UNDER AHU-12 AND VICE
 VERSA. PLEASE REFER TO THE SUBMITTED AC SUMMARY
 CALCULATIONS, AND THE AC LAYOUT PLAN ON SHEET M-101
 WHERE THE SYSTEMS APPEAR TO BE MISLABELED.
  
 4) M-001: EDUCATIONAL SCIENCE LABORATORIES REQUIRE
 EXHAUST SYSTEMS AT A RATE OF 50CFM'S PER SF. PLEASE
 CLARIFY WHAT TYPE OF ACTIVITIES WILL BE CONDUCTED IN
 THE SCIENCE ROOM, AND ALSO INDICATE IF THERE WILL BE AN
 ART CLASSROOM WHICH ALSO REQUIRES AND INDEPENDENT
 EXHAUST SYSTEM. REVISE THE PLANS TO SHOW COMPLIANCE.
  
 5) M-001: THE O/A SCHEDULE LISTS #122 AS "LARGE SPACE
 IN THE CENTER". PLEASE BE MORE SPECIFIC REGARDING THE
 USE OF THIS AREA. WHY WOULD THE O/A RATE FOR THIS AREA
 BE ANY LESS THAN THE PIAZZA?
  
 6) M-003: PLEASE CORRECT THE HVAC DESIGN TABLE
 INDICATING NO DUCT SMOKE DETECTORS.
  
 7) M-101: THE PLAN INDICATES 2360 CFM'S OF SUPPLY AIR
 FOR THE 4-TON SYSTEM WHICH IS CAPABLE OF PRODUCING
 MAXIMUM 1600 CFM'S ACCORDING TO THE AC SCHEDULE.
  
 8) M-101: THE EXHAUST IN ROOM 112A NEEDS TO BE
 INCREASED TO ACCOMODATE THE LOCKERS OR DRESSING AREA-
 TABLE 6-4 ASHRAE 62.1-10.
  
 9) M-102: PLEASE CLARIFY THE USE OF THE MOTORIZED
 DAMPER IN THE COMMON WALL BETWEEN CLASSROOMS 202 & 203.
  
 10) A050: REFER TO SECTION C101.4.4 FBC-14 ENERGY
 CONSERVATION. THE BUILDING CODE DATA INDICATES THE
 PROJECT IS A "CHANGE OF OCCUPANCY". PLEASE PROVIDE
 ENERGY CALCULATIONS.
  
 11) PROVIDE AC CALCULATIONS FOR THE WAC-1 SYSTEM.
  
 12) REFER TO SECTIONS C403.2.7.2 AND C403.2.7.3 FBC
 ENERGY CONSERVATION AND REPLACE THE WOOD DOORS ON THE
 MECHANICAL CLOSETS WITH NON-COMBUSTIBLE DOORS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER