2016-05-05 11:41:592001 SOUTH DIXIE HIGHWAY
 PERMIT #16041215
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW
 EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE
 BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE
 ORDERED FROM WWW.KNOXBOX.COM
  
 GENERAL: PROVIDE PANIC HARDWARE FOR ALL EGRESS DOORS
 SUBJECT TO 50 OR MORE PERSONS. SEVERAL DOORS MISSING
 PANIC HARDWARE INCLUDING DOORS 114, 114A, 114B, 119,
 121, 200 AND 204.
  
 SHEET A050 & SHEET A101: THESE SHEETS ARE IN CONFLICT
 WITH EACHOTHER. ONE SHEET INDICATES CLASSROOM AND THE
 OTHER SHEET INDICATES MULTI-PURPOSE USE. MULTI-PURPOSE
 ROOM #114 IS SHOWN UTILIZING AN OCCUPANT LOAD FACTOR 20
 SQUARE FEET PER PERSON IN LIEU OF 15 SQUARE FEET PER
 PERSON.
  
 SHEET A101: 2ND GRADE CLASSROOM #107 EGRESS DOOR
 APPEARS TO OBSTRUCT THE CORRIDOR. PER SECTION 7.2.1.4.3
 DOOR LEAF ENCROACHMENT - DURING ITS SWING, ANY DOOR
 LEAF IN A MEANS OF EGRESS SHALL LEAVE NOT LESS THAN
 ONE-HALF OF THE REQUIRED WIDTH OF AN AISLE, A CORRIDOR,
 A PASSAGEWAY, OR A LANDING UNOBSTRUCTED AND SHALL
 PROJECT NOT MORE THAN 7-INCHES INTO THE REQUIRED WIDTH
 OF AN AISLE, A CORRIDOR, A PASSAGEWAY, OR A LANDING,
 WHEN FULLY OPEN.
  
 SHEET A101: CORRIDOR EGRESS HAS THE POTENTIAL TO BE
 RESTRICTED WITH SECURITY DOOR/GRILL #100A. THIS IS NOT
 PERMITTED EVEN WITH FIRE ALARM INTEGRATION.
  
 SHEET A102: WHAT AGE GROUPS ARE INTENDED TO OCCUPY
 CLASSROOMS #202 AND #203.
  
 SHEET E101: CARD READER SHOWN ON EGRESS SIDE OF MAIN
 EXIT DOOR #100.
  
 SHEET E202: COULD NOT LOCATE EXTERIOR EMERGENCY
 LIGHTING FOR STAIR #2.
  
 GENERAL: IS ANY COMMERCIAL COOKING PROPSED AT THE
 SCHOOL?
  
 FIRE SPRINKLER: ENGINEERED FIRE SPRINKLER CONSTRUCTION
 DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT.
 AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE
 SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT. PER FLORIDA ADMINISTRATIVE CODE
 SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING
 DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE
 WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS
 APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD
 OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM
 TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP
 DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED
 INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS.
  