2016-05-05 11:41:59 | 2001 SOUTH DIXIE HIGHWAY |
| PERMIT #16041215 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW |
| EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE |
| BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE |
| ORDERED FROM WWW.KNOXBOX.COM |
| |
| GENERAL: PROVIDE PANIC HARDWARE FOR ALL EGRESS DOORS |
| SUBJECT TO 50 OR MORE PERSONS. SEVERAL DOORS MISSING |
| PANIC HARDWARE INCLUDING DOORS 114, 114A, 114B, 119, |
| 121, 200 AND 204. |
| |
| SHEET A050 & SHEET A101: THESE SHEETS ARE IN CONFLICT |
| WITH EACHOTHER. ONE SHEET INDICATES CLASSROOM AND THE |
| OTHER SHEET INDICATES MULTI-PURPOSE USE. MULTI-PURPOSE |
| ROOM #114 IS SHOWN UTILIZING AN OCCUPANT LOAD FACTOR 20 |
| SQUARE FEET PER PERSON IN LIEU OF 15 SQUARE FEET PER |
| PERSON. |
| |
| SHEET A101: 2ND GRADE CLASSROOM #107 EGRESS DOOR |
| APPEARS TO OBSTRUCT THE CORRIDOR. PER SECTION 7.2.1.4.3 |
| DOOR LEAF ENCROACHMENT - DURING ITS SWING, ANY DOOR |
| LEAF IN A MEANS OF EGRESS SHALL LEAVE NOT LESS THAN |
| ONE-HALF OF THE REQUIRED WIDTH OF AN AISLE, A CORRIDOR, |
| A PASSAGEWAY, OR A LANDING UNOBSTRUCTED AND SHALL |
| PROJECT NOT MORE THAN 7-INCHES INTO THE REQUIRED WIDTH |
| OF AN AISLE, A CORRIDOR, A PASSAGEWAY, OR A LANDING, |
| WHEN FULLY OPEN. |
| |
| SHEET A101: CORRIDOR EGRESS HAS THE POTENTIAL TO BE |
| RESTRICTED WITH SECURITY DOOR/GRILL #100A. THIS IS NOT |
| PERMITTED EVEN WITH FIRE ALARM INTEGRATION. |
| |
| SHEET A102: WHAT AGE GROUPS ARE INTENDED TO OCCUPY |
| CLASSROOMS #202 AND #203. |
| |
| SHEET E101: CARD READER SHOWN ON EGRESS SIDE OF MAIN |
| EXIT DOOR #100. |
| |
| SHEET E202: COULD NOT LOCATE EXTERIOR EMERGENCY |
| LIGHTING FOR STAIR #2. |
| |
| GENERAL: IS ANY COMMERCIAL COOKING PROPSED AT THE |
| SCHOOL? |
| |
| FIRE SPRINKLER: ENGINEERED FIRE SPRINKLER CONSTRUCTION |
| DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT. |
| AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE |
| SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS |
| (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS) |
| FOR A SUB-PERMIT. PER FLORIDA ADMINISTRATIVE CODE |
| SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING |
| DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE |
| WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS |
| APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD |
| OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM |
| TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP |
| DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED |
| INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS. |
| |