2016-05-04 14:43:01 | INITIAL ELECTRICAL PLAN REVIEW |
| |
| APPLICABLE CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70- 2011 NEC |
| COMMENTS: |
| |
| 1. PLEASE UPDATE ALL REFERENCES TO OLD FBC EC 505 TO |
| REFLECT NEW FBC ENERGY CONSERVATION C405.1 REQUIREMENTS |
| AND C405.7.4 COMPLETION REQUIREMENTS-(DRAWINGS AND |
| MANUALS. SEE VERBIAGE IN THE CODE. |
| 2. PROVIDE A SHOW ON PLANS THE VOLTAGE DROP |
| CALCULATIONS FOR FEEDER AND BRANCH CIRCUITS PER FBC EC |
| C405.7 ELECTRICAL POWER MANDATORY |
| 3. NOTE REGARDING SEPARATE PERMIT FOR UTILITY |
| TRANSFORMER WILL NOT SUFFICE FOR REVIEW APPROVAL AS WE |
| NEED TO DETERMINE THAT THE AVAILABLE FAULT CURRENT AT |
| TRANSFORMER FROM THE UTILITY TO CERTIFY OUT THAT THE |
| EQUIPMENT AIC RATINGS SHOWN IS WITHIN COMPLIANCE. |
| 4. ADDRESS ALL AND ANY FIRE DEPARTMENT COMMENTS RELATED |
| TO THE ELECTRICAL SCOPE. |
| 5. LABEL THE ONE-LINE SERVICE RISER MAINS TO BE RATED |
| FOR SERVICE ENTRANCE. A NOTE WILL SUFFICE. |
| 6. PROVIDE A GENERAL NOTE TO INDICATE NEC 110.16 ARC |
| FLASH HAZARD WARNINGS- A NOTE WILL SUFFICE. |
| 7. PER NEC 110.24 A AND B. INDICATE ON PLANS REQUIRED |
| FIELD MARKING OF THE AVAILABLE FAULT CURRENT DUE TO |
| MODIFICATIONS. |
| 8. SEPARATE PERMITS REQUIRED FOR ALL LOW VOLTAGE |
| SYSTEMS AND FIRE ALARM. PROVIDE A NOTE |
| 9. LABEL ALL RECEPTACLES WITHIN 6FT OF SINKS TO BE GFCI |
| PROTECTED. SEE POWER SHEET. NEC 210.8B7 |
| 10. PLEASE CLARIFY THE LOCATION OF THE ELECTRICAL PANEL |
| BOARDS, PER NEC 110.26 CLEARANCE REQUIREMENTS TO BE |
| MAINTAINED |
| 11. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. |
| PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY |
| QUESTIONS REGARDING THIS PROJECT. |
| |