2016-05-04 14:43:01INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE UPDATE ALL REFERENCES TO OLD FBC EC 505 TO
 REFLECT NEW FBC ENERGY CONSERVATION C405.1 REQUIREMENTS
 AND C405.7.4 COMPLETION REQUIREMENTS-(DRAWINGS AND
 MANUALS. SEE VERBIAGE IN THE CODE.
 2. PROVIDE A SHOW ON PLANS THE VOLTAGE DROP
 CALCULATIONS FOR FEEDER AND BRANCH CIRCUITS PER FBC EC
 C405.7 ELECTRICAL POWER MANDATORY
 3. NOTE REGARDING SEPARATE PERMIT FOR UTILITY
 TRANSFORMER WILL NOT SUFFICE FOR REVIEW APPROVAL AS WE
 NEED TO DETERMINE THAT THE AVAILABLE FAULT CURRENT AT
 TRANSFORMER FROM THE UTILITY TO CERTIFY OUT THAT THE
 EQUIPMENT AIC RATINGS SHOWN IS WITHIN COMPLIANCE.
 4. ADDRESS ALL AND ANY FIRE DEPARTMENT COMMENTS RELATED
 TO THE ELECTRICAL SCOPE.
 5. LABEL THE ONE-LINE SERVICE RISER MAINS TO BE RATED
 FOR SERVICE ENTRANCE. A NOTE WILL SUFFICE.
 6. PROVIDE A GENERAL NOTE TO INDICATE NEC 110.16 ARC
 FLASH HAZARD WARNINGS- A NOTE WILL SUFFICE.
 7. PER NEC 110.24 A AND B. INDICATE ON PLANS REQUIRED
 FIELD MARKING OF THE AVAILABLE FAULT CURRENT DUE TO
 MODIFICATIONS.
 8. SEPARATE PERMITS REQUIRED FOR ALL LOW VOLTAGE
 SYSTEMS AND FIRE ALARM. PROVIDE A NOTE
 9. LABEL ALL RECEPTACLES WITHIN 6FT OF SINKS TO BE GFCI
 PROTECTED. SEE POWER SHEET. NEC 210.8B7
 10. PLEASE CLARIFY THE LOCATION OF THE ELECTRICAL PANEL
 BOARDS, PER NEC 110.26 CLEARANCE REQUIREMENTS TO BE
 MAINTAINED
 11. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL.
 PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II