Plan Review Notes
Plan Review Notes For Permit 16041150
Permit Number 16041150
Review Stop E
Sequence Number 2
Notes
Date Text
2016-07-27 10:34:10REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
  
  
 1) OUTLETS SUPPLYING POOL PUMP MOTORS CONNECTED TO
 SINGLE-PHASE, 120 VOLT THROUGH 240 VOLT BRANCH
 CIRCUITS, RATED 15 OR 20 AMPERES, WHETHER BY RECEPTACLE
 OR BY DIRECT CONNECTION, SHALL BE PROVIDED WITH
 GROUND-FAULT CIRCUITINTERRUPTER PROTECTION FOR
 PERSONNEL.
 - SHOW GFCI PROTECTION ON THE ELECTRICAL DIAGRAM.