Plan Review Notes For Permit 16041150 |
Permit Number |
16041150 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-07-27 10:34:10 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | | | | | | | 1) OUTLETS SUPPLYING POOL PUMP MOTORS CONNECTED TO | | SINGLE-PHASE, 120 VOLT THROUGH 240 VOLT BRANCH | | CIRCUITS, RATED 15 OR 20 AMPERES, WHETHER BY RECEPTACLE | | OR BY DIRECT CONNECTION, SHALL BE PROVIDED WITH | | GROUND-FAULT CIRCUITINTERRUPTER PROTECTION FOR | | PERSONNEL. | | - SHOW GFCI PROTECTION ON THE ELECTRICAL DIAGRAM. |
|