Plan Review Notes
Plan Review Notes For Permit 16041150
Permit Number 16041150
Review Stop P
Sequence Number 1
Notes
Date Text
2016-05-20 06:33:251) THE PLANS SHOW THE POOL WATER WASTE DISCHARGE TO THE
 SANITARY SEWER.POOL WATER CANNOT DISCHARGE TO THE
 SANITARY OR STORM SYSTEM PER WPB CITY ORD. SECS. 90-126
 (5), 90-203 (A), 90-204, AND 90-205 (1). THE RESPONSE
 FROM THE ENGINEER OF RECORD STATES THAT THIS ISSUE HAS
 BEEN RESOLVED AND THE WASTE WATER WILL GO TO THE
 SANITARY. I DO NOT HAVE ANY DOCUMENTATION THAT THIS
 WILL BE ALLOWED.
 2) THE HYDRAULIC CALCULATIONS THAT WERE DONE ON SHT. 4
 TO REDUCE THE CAPACITY OF THE COLLECTOR TANKS WERE
 BASED ON A FLOW RATE OF 185 GPM BUT THE FLOW RATE ON
 SHT.1 IN THE POOL DATA TABLE SHOWS A FLOW RATE OF 155
 GPM. CLARIFY.
 3) THERE WAS NO MSDS DOCUMENTATION ATTACHED TO THE
 RESPONSE LETTER FROM THE ENGINEER AS NOTED IN HIS
 RESPONSE TO COMMENT # 8. CLARIFY.
 4) THERE WERE NO SPECIFICATIONS SUBMITTED FOR THE POOL
 HEATER. THIS INFORMATION CAN BE SUBMITTED WHEN THE GAS
 PERMIT IS SUBMITTED.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  