Plan Review Notes
Plan Review Notes For Permit 16041150
Permit Number 16041150
Review Stop E
Sequence Number 1
Notes
Date Text
2016-06-20 08:56:06REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 - PROVIDE SPECS ON POOL EQUIPMENT POOL HEATERS AND POOL
 PUMPS. FBC 107 INSUFFICIENT DOCUMENTS.
  
 - SPECIFY WHETHER LIGHT NICHE REQUIRES # 8 AWG BONDING
 CONDUCTOR OR NOT ? NEC 680.22(B)(2)/680.24, IF NOT HOW
 WILL POOL WATER BE BONDED ? NEC 680.26(C)
  
 - GENERAL COMMENT GFC PROTECTION REQUIRED FOR POOL
 PUMPS , LIGHTS , RECEPTACLES. NEC 680.21, 680.22.
  
  