2017-01-24 15:36:486TH REVIEW FBC-2014 MECHANICAL
 PERMIT #16041147
 1/24/17
  
 1) THE ELECTRICAL PLANS AND THE REVISED AC AND ENERGY
 CALCULATIONS DO NOT MATCH. THE PLANS INDICATE 5 WALL
 SYSTEMS LOCATED IN THE LIVING ROOMS OF UNITS 1-5. THE
 REVISED CALCULATIONS ARE FOR 15 WALL SYSTEMS TO BE
 LOCATED APPARENTLY IN THE LIVING ROOMS AND BEDROOMS OF
 THE UNITS. PLEASE NOTE THAT THE PANEL SCHEDULES ARE
 INDICATING ONLY FIVE WALL SYSTEMS.
  