2016-11-10 11:12:264TH REVIEW FBC-2014 MECHANICAL
 PERMIT #16041147
 11/10/16
  
 1) AS PREVIOUSLY REQUESTED, THE OWNER'S SIGNATURE IS
 REQUIRED TO BE ON THE ENERGY FORMS, AND THE MAKE AND
 MODEL NUMBERS OF THE AC SYSTEMS SHALL BE ON THE PLANS.
  
 2) THE AC CALCULATIONS DO NOT APPEAR TO BE FOR THE
 PROPOSED PROJECT BECAUSE THEY ARE LISTING THE PROJECT
 TITLE AS "MONTOYA RESIDENCE" WITH A STUART ADDRESS, AND
 THE CALCULATIONS ARE FOR ONLY 3 SYSTEMS. THE PROJECT
 UNDER REVIEW HAS 5 SYSTEMS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER